| Plan Review Notes For Permit 06030925 |
| Permit Number |
06030925 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-18 00:00:00 | ***DENIED*** | | | | | | 1) ADDRESS IS REQUIRED ON BUILDING THAT | | | SHALL BE MINIMUM OF 6" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND. PLEASE | | | ADD NOTE TO ELEVATIONS IF NEW OR | | | EXISTING. | | | | | | 2) PLEASE PROVIDE MORE DETAILS REGARDING | | | PAINT MIXING ROOM. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR PAINT SPRAY BOOTH. ALL WORK | | | SHALL COMPLY WITH NFPA 33. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT LOCATIONS TO | | | MEET HAZARD AND MINIMUM 75' TRAVEL | | | DISTANCE REQUIREMENTS. | | | | | | 5) PLEASE SHOW LOCATION(S) OF DUCT SMOKE | | | DETECTORS. IF BUILDING HAS A FIRE ALARM | | | SYSTEM, DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 6) LIFE SAFETY TO COMPLY WITH NFPA 101, | | | 2003 EDITION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|