| Plan Review Notes For Permit 06030925 |
| Permit Number |
06030925 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-14 00:00:00 | ***** UNSAT ***** | | | | | | 1) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF | | | TIME CLOCK BEING INSTALLED FOR LIGHTING | | | CONTROL SYSTEM. IS THIS AN ASTRONOMICAL | | | TYPE OF CLOCK? | | | FBC CHAPTER 13. 13-415.1.ABC.1.1 | | | PLEASE PROVIDE SCHEDULE FOR RELAY PANEL | | | /DETAIL FOR THIS. | | | | | | 2) NOTE: PLEASE SUBMIT MANUFACTURES | | | SPECS/CUT SHEETS FOR ATS WHICH IS BEING | | | INSTALLED FOR FUTURE GEN. | | | 215.5 | | | | | | 3) NOTE: PLEASE CLARIFY THE MEANS OF | | | DISCONNECT WHICH WILL BE REQUIRED FOR | | | GEN FEEDERS. IS THE MDP PANEL GROUPED | | | WITH THE MAIN AND ATS? IF THE MDP IS | | | GROUPED AND CONTAINS A MCB FOR | | | DISCONNECTING POWER THEN A SEPARATE | | | DISCONNECT WOULD NOT BE REQUIRED. | | | PLEASE INDICATE THE LOCATION ON PLANS OF | | | THE MDP AND ATS. | | | 215.5,225.31-225.39 | | | | | | 4) NOTE: PLEASE VERIFY NEW SERVICE AS | | | SHOWN. PLANS INDICATE AN EXISTING | | | SERVICE AND MAIN. IT IS NOT KNOWN AT | | | THIS TIME IF AN ADDITIONAL SERVICE IS | | | PERMITTED PER 230.2 | | | | | | 5) NOTE: PLEASE SEE 700.12E FOR | | | CICUITING OF EM/EXT LTS. | | | *EXCPT* | | | | | | 6) NOTE: PLEASE CLARIFY IF THE | | | CONTINUOUS / LIGHTING LOADS ARE SHOWN AT | | | 125%.215.3,230.42 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALLL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|