| 2006-05-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:06030925 |
| | ADD: 433 AVON RD |
| | CONT: BURCHANDT CONSTRUCTION |
| | TEL: (561)718-2602 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUM- BER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICA TION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 3) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 4) WPB ADMIN105.9* |
| | FL S S 469. THIS AGENCY IS THE LOCAL |
| | ASBESTOS AUTHORITY, AND SHOULD RECEIVE |
| | ALL NOTIFICATIONS FOR BUILDING |
| | DEMOLITION OR RENOVATION PROJECTS. |
| | CONTACT THEM FOR GENERAL INFORMATION ON |
| | ASBESTOS ISSUES INCLUDING REGULATIONS, |
| | CONTRACTORS OR CONSULTANTS.FL SS 469.003 |
| | PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENVIROMENTAL SCIENCE & |
| | ENGINEERING AIR POLLUTION CONTROL |
| | SECTION) |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561)366-3070 |
| | |
| | 5) SHEET A-1: |
| | 5A) WEST ELEVATION, PROVIDE INFORMATION |
| | HOW CLOSE THIS BUILDING IS TO THE |
| | PROPERTY LINE? TABLE TABLE 602. |
| | |
| | 5B) PLANS INDICATE A PROPOSED PAINT |
| | SPRAY BOOTH, PROVIDE DETAIL SHEETS. |
| | |
| | 5C) PLANS INDICATE NEW WALLS ABOVE THE |
| | RESTROOMS, A EQUIPMENT PLATFORM. DETAIL# |
| | 8 DOESN'T INDICATE IF THE METAL STUDS |
| | ARE DRYWALL OR STRUCTURAL RATED? |
| | ARE THE STAIRS GOING TO THE PLATFORM NEW |
| | ALSO? NO DETAILS? |
| | 505.5 INDUSTRIAL EQUIPMENT PLATFORMS. |
| | INDUSTRIAL EQUIPMENT PLATFORMS IN |
| | BUILDINGS SHALL NOT BE CONSIDERED AS A |
| | PORTION OF THE FLOOR BELOW. SUCH |
| | EQUIPMENT PLATFORMS SHALL NOT CONTRIBUTE |
| | TO EITHER THE BUILDING AREA OR THE |
| | NUMBER OF STORIES AS REGULATED BY |
| | SECTION 503.1 . THE AREA OF THE |
| | INDUSTRIAL EQUIPMENT PLATFORM SHALL NOT |
| | BE INCLUDED IN DETERMINING THE FIRE |
| | AREA. INDUSTRIAL EQUIPMENT PLATFORMS |
| | SHALL NOT BE A PART OF ANY MEZZANINE, |
| | AND SUCH PLATFORMS AND THE WALKWAYS, |
| | STAIRS AND LADDERS PROVIDING ACCESS TO |
| | AN EQUIPMENT PLATFORM SHALL NOT SERVE AS |
| | A PART OF THE MEANS OF EGRESS FROM THE |
| | BUILDING. |
| | |
| | 505.5.1 AREA LIMITATIONS. |
| | THE AGGREGATE AREA OF ALL INDUSTRIAL |
| | EQUIPMENT PLATFORMS WITHIN A ROOM SHALL |
| | NOT EXCEED TWO-THIRDS OF THE AREA OF THE |
| | ROOM IN WHICH THEY OCCUR. WHERE AN |
| | EQUIPMENT PLATFORM IS LOCATED IN THE |
| | SAME ROOM AS A MEZZANINE, THE AREA OF |
| | THE MEZZANINE SHALL BE DETERMINED BY |
| | SECTION 505.2 , AND THE COMBINED |
| | AGGREGATE AREA OF THE EQUIPMENT |
| | PLATFORMS AND MEZZANINES SHALL NOT |
| | EXCEED TWO-THIRDS OF THE ROOM IN WHICH |
| | THEY OCCUR. |
| | |
| | 6) THE SOUTHEAST CORNER OF THE BUILDING |
| | A PLATFORM AND STAIRWAY ARE CONSTRUCTED, |
| | PROVIDE MORE DETAILS? |
| | |
| | 7A)1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 7B) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 7C) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7D) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 1) WINDOWS |
| | 2) MOTORIZED OVERHEAD DOORS |
| | 3) STOREFRONT WINDOWS |
| | 4) STOREFRONT DOORS |
| | 5) MULLIONS |
| | |
| | 8) PROVIDE INFORMATION ON COMPLIANCE |
| | WITH TABLE 302.1.1PAINT SHOP 2HR |
| | SEPERATION OR 1HR AND PROVIDE AUTOMATIC |
| | FIRE -EXTINGUISHING SYSTEM. |
| | |
| | 9) PROVIDE THE AMOUNT OF PAINT AND |
| | SOLVENTS TO BE STORED ON SITE AND |
| | FLAMMIBLITY, THIS WILL DICTATE OCCUPANCY |
| | SEE CONTROL AREAS TABLE 307.7(1) |
| | |
| | 10) PROVIDE MSDS SHEETS FOR THE ABOVE |
| | MATERIALS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |