| Plan Review Notes For Permit 06030897 |
| Permit Number |
06030897 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-13 00:00:00 | ******DENIED****** | | | | | | 1) SPEC SHEETS INDICATE DUCT SMOKE | | | DETECTORS, HOWEVER NONE ARE SHOWN ON THE | | | PLANS OR RISER. | | | | | | 2) IT APPEARS THAT ONLY (1) SET OF SPEC | | | SHEETS WERE SUBMITTED. PLEASE SUBMIT | | | SHEETS WITH EACH SET OF DRAWINGS. IF (2) | | | SETS WERE SUBMITTED, PLEASE SEPARATE. | | | | | | 3) FIRE ALARM SHALL BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE. | | | | | | 4) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 5) FIRE ALARM TO BE CLASS A OR FULLY | | | ADDRESSABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|