 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) SHT A-1 CODE INFORMATION: REFERE TO
 FBC 2004 CODES.
 2) SHT A-1 INDEX OF DRAWINGS PLUMBING
 PLANS NOT INCLUDED IN THIS SET.
 3) SHT A-9 ROOF PLAN, CH 11 STORM
 DRAINAGE. PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINAGE, WITH
 ISOMETRIC DRAWINGS, ALL PIPE SIZES.
 4) OFFICE REST ROOM SEC 11-4.1.3 (11)
 (11) TOILET FACILITIES. IF TOILET ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF
 SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE) SHALL BE ADAPTABLE. IF BATHING
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. ACCESSIBLE TOILET ROOMS
 AND BATHING FACILITIES SHALL BE ON AN
 ACCESSIBLE ROUTE.
 5) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  