| Plan Review Notes For Permit 06030895 |
| Permit Number |
06030895 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-20 00:00:00 | *** DENIED *** | | | 1) MECHANICAL PLANS PAGE M-1 AND M-2 | | | NEED THE ARCHITECTURE'S SEAL ON THEM, | | | PER FAC 61G1-16.003 . | | | | | | 2) SHOW DETAILS FOR ANCHORING THE RTU'S | | | TO THE ROOF. | | | | | | 3) OUTDOOR AIR REQUIREMENTS ARE NOT INT. | | | MECH. CODE, BUT ARE TO 2004 FBC MECH.. | | | | | | 4) OUTDOOR AIR OCCUPANCY: IS NOT | | | RESTAURANT - DINNING ROOM, BUT IS LISTED | | | UNDER SPECIALTY SHOPS AS SUPERMARKETS. | | | PLEASE CORRECT AND RE-CALCULATE OUTDOOR | | | AIR REQUIREMENTS (MY ESTIMATION IS 1740 | | | CFM'S + MAKE UP AIR). | | | | | | 5) PLEASE EXPLAIN FOR OUTDOOR AIR | | | PROVIDED, WHAT DOES (GF-1,2,3,4,5,6 | | | FCU-1,2,3) REPRESENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|