Plan Review Notes
Plan Review Notes For Permit 06030895
Permit Number 06030895
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-05-17 00:00:00***DENIED***
  
 1) AN ADDRESS IS REQUIRED ON THE
 BUILDING, AND SHALL BE MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND. PLEASE SHOW ON ELEVATIONS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED, AND SHALL BE MOUNTED AT
 LOCATIONS NOT TO EXCEED THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 3) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A,B OR C.
  
 4) PLEASE SEE MECHANICAL REVIEW NOTE #4
 IN REFERENCE TO OCCUPANCY TYPE. PLEASE
 PROVIDE OCCUPANCY TYPE ON PLANS WITH
 CALCULATED OCCUPANT LOADS.
  
 5) NO MENTION OF FIRE PROTECTION SYSTEMS
 FOR THIS BUILDING. PLEASE SEE NFPA 101,
 SECTION 36.3.5.1 (2) REGARDING REQUIRED
 FIRE SPRINKLER SYSTEMS IN ALL MERCANTILE
 OCCUPANCIES EXCEEDING 12,000 SQ' IN
 GROSS AREA.
  
 6) PLEASE PROVIDE A LIFE SAFETY PLAN
 ILLUSTRATING THE ARRANGEMENT OF MEANS OF
 EGRESS. LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 7) EXIT DOORS SERVING AREAS WITH
 OCCUPANT LOADS OF 100 OR MORE, SHALL BE
 INSTALLED WITH APPROVED PANIC HARDWARE.
 PLEASE PROVIDE MORE DETAILS FOR EXIT
 DOORS ON SCHEDULE.
  
 8) PLEASE ILLUSTRATE THE LOCATION OF ALL
 EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES. LIGHTING PLAN DOES NOT SHOW
 AN EXIT SIGN ABOVE THE NORTH EXIT DOOR.
  
 9) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
 DEBRIS SHALL BE CLEANED FROM THE SITE
 DAILY.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  