| 2006-05-17 00:00:00 | ***DENIED*** |
| | |
| | 1) AN ADDRESS IS REQUIRED ON THE |
| | BUILDING, AND SHALL BE MINIMUM OF 6" IN |
| | HEIGHT AND CONTRASTING TO THE |
| | BACKGROUND. PLEASE SHOW ON ELEVATIONS. |
| | |
| | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| | REQUIRED, AND SHALL BE MOUNTED AT |
| | LOCATIONS NOT TO EXCEED THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 3) PLEASE PROVIDE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN TERMS OF CLASS A,B OR C. |
| | |
| | 4) PLEASE SEE MECHANICAL REVIEW NOTE #4 |
| | IN REFERENCE TO OCCUPANCY TYPE. PLEASE |
| | PROVIDE OCCUPANCY TYPE ON PLANS WITH |
| | CALCULATED OCCUPANT LOADS. |
| | |
| | 5) NO MENTION OF FIRE PROTECTION SYSTEMS |
| | FOR THIS BUILDING. PLEASE SEE NFPA 101, |
| | SECTION 36.3.5.1 (2) REGARDING REQUIRED |
| | FIRE SPRINKLER SYSTEMS IN ALL MERCANTILE |
| | OCCUPANCIES EXCEEDING 12,000 SQ' IN |
| | GROSS AREA. |
| | |
| | 6) PLEASE PROVIDE A LIFE SAFETY PLAN |
| | ILLUSTRATING THE ARRANGEMENT OF MEANS OF |
| | EGRESS. LIFE SAFETY SHALL COMPLY WITH |
| | NFPA 101, 2003 EDITION. |
| | |
| | 7) EXIT DOORS SERVING AREAS WITH |
| | OCCUPANT LOADS OF 100 OR MORE, SHALL BE |
| | INSTALLED WITH APPROVED PANIC HARDWARE. |
| | PLEASE PROVIDE MORE DETAILS FOR EXIT |
| | DOORS ON SCHEDULE. |
| | |
| | 8) PLEASE ILLUSTRATE THE LOCATION OF ALL |
| | EXIT SIGNS AND EMERGENCY LIGHTING |
| | FACILITIES. LIGHTING PLAN DOES NOT SHOW |
| | AN EXIT SIGN ABOVE THE NORTH EXIT DOOR. |
| | |
| | 9) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | DEBRIS SHALL BE CLEANED FROM THE SITE |
| | DAILY. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |