Plan Review Notes
Plan Review Notes For Permit 06030895
Permit Number 06030895
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE MIN PLANS AND DESIGN
 SHALL BE UNDER THE 2004 FBC WHICH WAS
 ADOPTED ON OCT 1ST, 2005
 PLEASE ALSO BE SURE PLANS REFERENCE THE
 FOLLOWING CODES.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101
  
 2) NOTE: PLEASE SEE MECH SHEETS WHICH
 ARE NOT SIGNED, DATED OR SEALED BY A
 DESIGN PROFESSIONAL AS STATED ON PLANS.
 FS 481.221, 471.025
  
 3) NOTE: PLEASE SEE SEAL FOR ENGINEER
 WITH THE WORDING OF "CERTIFICATE" HAS
 EXPIRED FOR USE. PLEASE SEE FAC
 61G15-23.001, WHICH REQUIES THE SEAL TO
 INDICATE THE WORDING OF "LICENSE". THIS
 WAS PASSED IN FEB 04 AND AN EXTENSION
 WAS GRANTED TO THE DATE OF DEC 30TH,
 2005.
 SEAL IS TO BE UPADTED.
  
 4) NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS.
 PLEASE INDICATE ALL.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 & .2, & .3
 ALL DEVICES, TYPE OF SYSTEM, SCHEDULING
 ETC TO BE PROVIDED ON PLANS AND SPECS
 FOR A LIGHTING CONTROL SYSTEM INDICATING
 A LISTING FROM A NRTL.
 PLEASE SEE 13-415.1.AB.1 FOR MIN
 LIGHTING CALCULATIONS TO BE PROVIDED.
 PLEASE SEE 13-413.1ABC.1 FOR WORST CASE
 SCENERIO TO BE PROVIDED FOR VD/ CALCS.
  
 6) NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST
 MEANS OF DISCONNECT. 250.110,250.24B
 250.122 ETC.
 PLEASE CALRIFY RISERS AND SCHEDULES AS
 PLANS INDICATE A "GRND"? IS THIS THE
 NEUTRAL? THIS IS ASSUMED DUE TO THE SIZE
 OF CONDUCTORS ETC.
 215.5
  
 7) NOTE: PLEASE SEE 240.4C FOR DEVICES
 OVER 800A'S. PLEASE SEE 110.14, 310.16
 FOR MIN SEC'S AND FEEDERS.
  
 8) NOTE: PLEASE SEE NFPA-101 7.8,7.9 FOR
 EM LTS REQUIRED AND BACK UP OF FIXTURES
 TO PROVIDE MIN EGRESS FT CANDLES TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE SEE FIRE REVIEW COMMENTS AS
 LOCATIONS SHALL MEET FIRE MARSHAL'S
 OFFICE ALSO.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 THESE FIXTURES TO LOCAL LIGHTING BRANCH
 CIRCUIT.
  
 9) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3,230.42
  
 10) NOTE: PLEASE SEE RISER MENTIONS TO
 TAKE THE GROUNDING ELECTRODE CONDUCTOR
 TO THE EXISTING FOUNDATION STEEL. PLEASE
 KNOW, IF THIS IS AN EXISTING BUILDING
 AND THE ATTACHMENT IS NOT THERE, THIS IS
 NOT REQUIRED BY THIS AHJ. IN FACT, THIS
 MAY INDEED AFFECT THE STRUCTURAL
 STRENGTH OF THE EXISTING FOOTING. THIS
 MAY BE DONE , HOWEVER THIS IS NOT
 REQUIRED,
 ** PLEASE KNOW, IF SHOWN ON PLANS/RISER
 THEN THIS WILL BE REQUIRED.
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 *** BEFORE RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVED ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO SETS FOR REVIEW AND
 STAMPIN.
 ONLY ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717