| 2006-04-12 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE MIN PLANS AND DESIGN |
| | SHALL BE UNDER THE 2004 FBC WHICH WAS |
| | ADOPTED ON OCT 1ST, 2005 |
| | PLEASE ALSO BE SURE PLANS REFERENCE THE |
| | FOLLOWING CODES. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE MECH SHEETS WHICH |
| | ARE NOT SIGNED, DATED OR SEALED BY A |
| | DESIGN PROFESSIONAL AS STATED ON PLANS. |
| | FS 481.221, 471.025 |
| | |
| | 3) NOTE: PLEASE SEE SEAL FOR ENGINEER |
| | WITH THE WORDING OF "CERTIFICATE" HAS |
| | EXPIRED FOR USE. PLEASE SEE FAC |
| | 61G15-23.001, WHICH REQUIES THE SEAL TO |
| | INDICATE THE WORDING OF "LICENSE". THIS |
| | WAS PASSED IN FEB 04 AND AN EXTENSION |
| | WAS GRANTED TO THE DATE OF DEC 30TH, |
| | 2005. |
| | SEAL IS TO BE UPADTED. |
| | |
| | 4) NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS. |
| | PLEASE INDICATE ALL. |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1 & .2, & .3 |
| | ALL DEVICES, TYPE OF SYSTEM, SCHEDULING |
| | ETC TO BE PROVIDED ON PLANS AND SPECS |
| | FOR A LIGHTING CONTROL SYSTEM INDICATING |
| | A LISTING FROM A NRTL. |
| | PLEASE SEE 13-415.1.AB.1 FOR MIN |
| | LIGHTING CALCULATIONS TO BE PROVIDED. |
| | PLEASE SEE 13-413.1ABC.1 FOR WORST CASE |
| | SCENERIO TO BE PROVIDED FOR VD/ CALCS. |
| | |
| | 6) NOTE: PLEASE INDICATE THE EQUIPMENT |
| | GROUNDING CONDUCTORS AFTER THE FIRST |
| | MEANS OF DISCONNECT. 250.110,250.24B |
| | 250.122 ETC. |
| | PLEASE CALRIFY RISERS AND SCHEDULES AS |
| | PLANS INDICATE A "GRND"? IS THIS THE |
| | NEUTRAL? THIS IS ASSUMED DUE TO THE SIZE |
| | OF CONDUCTORS ETC. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE 240.4C FOR DEVICES |
| | OVER 800A'S. PLEASE SEE 110.14, 310.16 |
| | FOR MIN SEC'S AND FEEDERS. |
| | |
| | 8) NOTE: PLEASE SEE NFPA-101 7.8,7.9 FOR |
| | EM LTS REQUIRED AND BACK UP OF FIXTURES |
| | TO PROVIDE MIN EGRESS FT CANDLES TO THE |
| | PUBLIC RIGHT OF WAY. |
| | PLEASE SEE FIRE REVIEW COMMENTS AS |
| | LOCATIONS SHALL MEET FIRE MARSHAL'S |
| | OFFICE ALSO. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | THESE FIXTURES TO LOCAL LIGHTING BRANCH |
| | CIRCUIT. |
| | |
| | 9) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AND LARGEST MOTOR LOADS AT 125%. |
| | 215.3,230.42 |
| | |
| | 10) NOTE: PLEASE SEE RISER MENTIONS TO |
| | TAKE THE GROUNDING ELECTRODE CONDUCTOR |
| | TO THE EXISTING FOUNDATION STEEL. PLEASE |
| | KNOW, IF THIS IS AN EXISTING BUILDING |
| | AND THE ATTACHMENT IS NOT THERE, THIS IS |
| | NOT REQUIRED BY THIS AHJ. IN FACT, THIS |
| | MAY INDEED AFFECT THE STRUCTURAL |
| | STRENGTH OF THE EXISTING FOOTING. THIS |
| | MAY BE DONE , HOWEVER THIS IS NOT |
| | REQUIRED, |
| | ** PLEASE KNOW, IF SHOWN ON PLANS/RISER |
| | THEN THIS WILL BE REQUIRED. |
| | |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | *** BEFORE RESUBMITTING PLANS, PLEASE |
| | COMPLETELY REMOVED ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO SETS FOR REVIEW AND |
| | STAMPIN. |
| | ONLY ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |