2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06030895
 ADD: 5011 BROADWAY AV
 CONT: A&M BUILDERS
 TEL: (561)305-1605
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 SHEET A-1:
  
 1) WRONG ADDITION OF THE CODE.
 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. FOOTPRINT
 H) SQ. FT. UNDER ROOF (TOTAL)
 I) OCCUPANT LOAD
 J) FLOOD ZONE
 K) THERE IS NO TABLE 600 UNDER 2004
 CODE.
  
 2) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) AUTOMATIC SLIDING DOORS
 B) SHUTTERS
 C) PREFABRICATED A/C STANDS
  
 7A) MISSING INFO FOR ROOFING REPORT :
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
  
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 7B) ROOF TILE, CONTRACTOR DIDN'T CIRCLE
 WHICH TYPE OF FASTENING SYSTEM THAT WILL
 BE USED.
  
 7C) NO INFORMATION FOR FASTENING OF HIP
 BOARD OR HIP TILE.1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS
 OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08-05 (FOURTH EDITION).
  
 8) FLOOR PLAN A-4 INDICATES USE OF POWER
 HORIZONTAL SLIDING DOORS. SHOW
 COMPLIANCE WITH:
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES,
 HORIZONTAL SLIDING DOORS PERMITTED TO BE
 A COMPONENT OF A MEANS OF EGRESS IN
 ACCORDANCE WITH EXCEPTION 5 TO SECTION
 1008.1.2 SHALL COMPLY WITH ALL OF THE
 FOLLOWING CRITERIA:
 1.THE DOORS SHALL BE POWER OPERATED
 AND SHALL BE CAPABLE OF BEING OPERATED
 MANUALLY IN THE EVENT OF POWER FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A
 SIMPLE METHOD FROM BOTH SIDES WITHOUT
 SPECIAL KNOWLEDGE OR EFFORT.
 3.THE FORCE REQUIRED TO OPERA TE
 THE DOOR SHALL NOT EXCEED 30 POUNDS (133
 N) TO SET THE DOOR IN MOTION AND 15
 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN
 IT TO THE MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A
 FORCE NOT TO EXCEED 15 POUNDS (67 N)
 WHEN A FORCE OF 250 POUNDS (1100 N) IS
 APPLIED PERPENDICULAR TO THE DOOR
 ADJACENT TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY
 WITH THE APPLICABLE FIRE PROTECTION
 RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY
 SMOKE DETECTION, SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 80 AND SHALL COMPLY
 WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN
 INTEGRATED STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY
 SHALL BE ELECTRICALLY SUPERVISED.
  
 9) PLANS INDICATE THIS PROJECT IS TO BE
 PHASED, WILL THE WORK TO BE INCLUDED IN
 BOTH PHASES UNDER THIS PERMIT?
 IF SO CONTACT KEN CONRAD FOR
 REQUIREMENTS FOR PHASED WORK.805 6666.
  
 10A) SHEET A-6 INDICATES ON THE NORTH
 ELEVATION A MEZZANINE LEVEL FOR
 EQUIPMENT. THERE IS NO MENTION OF THIS
 IN THE NEW PLAN?
  
 10B) THE SAME NORTH ELEVATION INDICATES
 VENTS FOR THE EQUIPMENT ROOM, THERE IS
 NO DETAILS SHOWING VENTS FOR MEZZANINE
 LEVEL ON THE NEW ELEVATIONS.
  
 10C) 505.1 A MEZZANINE OR MEZZANINES IN
 COMPLIANCE WITH THIS SECTION SHALL BE
 CONSIDERED A PORTION OF THE FLOOR BELOW.
 SUCH MEZZANINES SHALL NOT CONTRIBUTE TO
 EITHER THE BUILDING AREA OR NUMBER OF
 STORIES AS REGULATED BY SECTION 503.1 .
 THE AREA OF THE MEZZANINE SHALL BE
 INCLUDED IN DETERMINING THE FIRE AREA
 DEFINED IN SECTION 702 . THE CLEAR
 HEIGHT ABOVE AND BELOW THE MEZZANINE
 FLOOR CONSTRUCTION SHALL NOT BE LESS
 THAN 7 FEET (2134 MM).
  
 10D) SHOW EGRESS REQUIREMENTS FOR THE
 MEZZANINE LEVEL.
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 11) 505.5 INDUSTRIAL EQUIPMENT
 PLATFORMS. INDUSTRIAL EQUIPMENT
 PLATFORMS IN BUILDINGS SHALL NOT BE
 CONSIDERED AS A PORTION OF THE FLOOR
 BELOW. SUCH EQUIPMENT PLATFORMS SHALL
 NOT CONTRIBUTE TO EITHER THE BUILDING
 AREA OR THE NUMBER OF STORIES AS
 REGULATED BY SECTION 503.1 . THE AREA OF
 THE INDUSTRIAL EQUIPMENT PLATFORM SHALL
 NOT BE INCLUDED IN DETERMINING THE FIRE
 AREA. INDUSTRIAL EQUIPMENT PLATFORMS
 SHALL NOT BE A PART OF ANY MEZZANINE ,
 AND SUCH PLATFORMS AND THE WALKWAYS,
 STAIRS AND LADDERS PROVIDING ACCESS TO
 AN EQUIPMENT PLATFORM SHALL NOT SERVE AS
 A PART OF THE MEANS OF EGRESS FROM THE
 BUILDING.
  
 505.5.1 AREA LIMITATIONS.
 THE AGGREGATE AREA OF ALL INDUSTRIAL
 EQUIPMENT PLATFORMS WITHIN A ROOM SHALL
 NOT EXCEED TWO-THIRDS OF THE AREA OF THE
 ROOM IN WHICH THEY OCCUR. WHERE AN
 EQUIPMENT PLATFORM IS LOCATED IN THE
 SAME ROOM AS A MEZZANINE , THE AREA OF
 THE MEZZANINE SHALL BE DETERMINED BY
 SECTION 505.2 , AND THE COMBINED
 AGGREGATE AREA OF THE EQUIPMENT
 PLATFORMS AND MEZZANINES SHALL NOT
 EXCEED TWO-THIRDS OF THE ROOM IN WHICH
 THEY OCCUR.
  
 12) STUCTURAL SHEETS MISSING STRUCTURAL
 ENGINEERS ADDRESS, SEE FAC
 61G15-23.002(2).
  
 13)S-2 DETAIL# 1 PLANS DO NOT PROVIDE
 BOLT PATTERN BASE PLATE, NOR THE LENGHT
 NOR TYPE OF ANCHOR.
  
 14) SHEET D-1 INDICATES THE USE OF EFIS
 IN THE HORIZONTAL POSITION PROVIDE
 PRODUCT APPROVAL FOR SUCH USAGE.
  
 15) PROVIDE INFORMATION ON THE WALK-IN
 COOLERS AND FREEZERS.
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM
 THICKNESS OF 10 INCHES (254 MM) IN
 COOLER AND FREEZER WALLS SHALL:
 1.HAVE A FLAME SPREAD INDEX OF 25
 OR LESS AND A SMOKE-DEVELOPED INDEX OF
 NOT MORE THAN 450, WHERE TESTED IN A
 MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND
 SELF-IGNITION TEMPERATURES OF NOT LESS
 THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN
 0.032-INCH (0.8 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM
 PLASTIC HAVING A THICKNESS THAT DOES NOT
 EXCEED 4 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE
 THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL
 HAVING A MINIMUM BASE METAL THICKNESS OF
 0.016 INCH (0.41 MM). A THICKNESS OF UP
 TO 10 INCHES (254 MM) IS PERMITTED WHERE
 PROTECTED BY A THERMAL BARRIER.
  
 16) PROVIDE INFORMATION FOR CHECK-OUT
 AISLES.11-7.3(2)-(4)
 (2)CLEAR AISLE WIDTH FOR ACCESSIBLE
 CHECK-OUT AISLES SHALL COMPLY WITH
 SECTION 11-4.2.1 AND MAXIMUM ADJOINING
 COUNTER HEIGHT SHALL NOT EXCEED 38
 INCHES (965 MM) ABOVE THE FINISH FLOOR.
 THE TOP OF THE LIP SHALL NOT EXCEED 40
 INCHES (1015 MM) ABOVE THE FINISH FLOOR.
  
 (3)SIGNAGE IDENTIFYING ACCESSIBLE
 CHECK-OUT AISLES SHALL COMPLY WITH
 SECTION 11-4.30.7 AND SHALL BE MOUNTED
 ABOVE THE CHECK-OUT AISLE IN THE SAME
 LOCATION WHERE THE CHECK-OUT NUMBER OR
 TYPE OF CHECK-OUT IS DISPLAYED.
 (4)ALL CUSTOMER CHECK-OUT AISLES
 NOT REQUIRED BY THIS CODE TO BE
 ACCESSIBLE SHALL HAVE AT LEAST 32 INCHES
 (813 MM) OF CLEAR PASSAGE.
  
 17) 11-7.4 SECURITY BOLLARDS.
 ANY DEVICE USED TO PREVENT THE REMOVAL
 OF SHOPPING CARTS FROM STORE PREMISES
 SHALL NOT PREVENT ACCESS OR EGRESS TO
 PEOPLE IN WHEELCHAIRS. AN ALTERNATE
 ENTRY THAT IS EQUALLY CONVENIENT TO THAT
 PROVIDED FOR THE AMBULATORY POPULATION
 IS ACCEPTABLE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  