Plan Review Notes
Plan Review Notes For Permit 06030890
Permit Number 06030890
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-08 00:00:00**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE A "SYSTEM" IS NOT
 BEING SHOWN FOR CONTROL AND SCHEDULING
 OF LIGHTING.
 PLEASE SEE THE OVER RIDE DEVIES SHOWN
 ARE OK AND ARE REQUIRED, HOWEVER PLEASE
 PROVIDE SPECS FOR UNITS BEING PROPOSED,
 AS THE DISTANCE NEEDS TO BE VERIFIED IF
 MOTION SENSORS ARE GOING TO BE USED FOR
 THE ENTIRE TENANT SPACE.NOT PART OF A
 NORMAL LIGHTING CONTROL SYSTEM.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2.
  
 2) NOTE: PLEASE SEE CONDUIT SIZES AHLL
 BE VERIFIED AND SPECIFIED ON RISER.
 PLEASE SEE CONDUIT FILL IS EXCEDDING ON
 RISER FOR 5- 4/0'S IN A 2" CONDUIT.
 TABLE 9, 215.5
 PLEASE VERIFY ALSO THE 4" CONDUIT SHOWN
 AS THIS SIZE INTO THE PANEL AS SHOWN
 DOES NOT SEEM LIKELY OR POSSIBLE.
  
 3) NOTE: PLEASE SEE A 3/0 IS BEING SHOWN
 FOR THE "EQUIPMENT GROUNDING
 CONDUCTOR"??
 3/0 SEEMS VERY LARGE AND ESP SINCE
 CONDUIT FILL IS EXCEEDED.
 PLEASE SEE 250.122 FOR SIZING WHICH MAY
 HELP IN CONDUIT SIZZING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]