| 2006-06-08 00:00:00 | **** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE A "SYSTEM" IS NOT |
| | BEING SHOWN FOR CONTROL AND SCHEDULING |
| | OF LIGHTING. |
| | PLEASE SEE THE OVER RIDE DEVIES SHOWN |
| | ARE OK AND ARE REQUIRED, HOWEVER PLEASE |
| | PROVIDE SPECS FOR UNITS BEING PROPOSED, |
| | AS THE DISTANCE NEEDS TO BE VERIFIED IF |
| | MOTION SENSORS ARE GOING TO BE USED FOR |
| | THE ENTIRE TENANT SPACE.NOT PART OF A |
| | NORMAL LIGHTING CONTROL SYSTEM. |
| | 13-415.1.ABC.1.1, 13-415.1.ABC.1.2. |
| | |
| | 2) NOTE: PLEASE SEE CONDUIT SIZES AHLL |
| | BE VERIFIED AND SPECIFIED ON RISER. |
| | PLEASE SEE CONDUIT FILL IS EXCEDDING ON |
| | RISER FOR 5- 4/0'S IN A 2" CONDUIT. |
| | TABLE 9, 215.5 |
| | PLEASE VERIFY ALSO THE 4" CONDUIT SHOWN |
| | AS THIS SIZE INTO THE PANEL AS SHOWN |
| | DOES NOT SEEM LIKELY OR POSSIBLE. |
| | |
| | 3) NOTE: PLEASE SEE A 3/0 IS BEING SHOWN |
| | FOR THE "EQUIPMENT GROUNDING |
| | CONDUCTOR"?? |
| | 3/0 SEEMS VERY LARGE AND ESP SINCE |
| | CONDUIT FILL IS EXCEEDED. |
| | PLEASE SEE 250.122 FOR SIZING WHICH MAY |
| | HELP IN CONDUIT SIZZING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |