| Plan Review Notes For Permit 06030890 |
| Permit Number |
06030890 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-18 00:00:00 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 2) SMOKE DETECTORS SHOWN ON NEW PANEL | | | SCHEDULE ON SHT A.2. IF THIS REFERS TO | | | DUCT SMOKE DETECTORS, NEW INSTALLATIONS | | | SHALL INITIATE A GENERAL FIRE ALARM IF | | | PROVIDED, IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | 3) ADDITIONAL 2A,-10B,C RATED FIRE | | | EXTINGUISHERS ARE REQUIRED IN PROXIMITY | | | OF EXIT DOORS IN SPACES #206 & #210. | | | | | | 4) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|