| 2006-04-12 00:00:00 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE WE ARE UNDER THE | | | 2004 FBC. PLEASE SEE CHAPTER 13 | | | 13-415.1.ABC.1.1 &.2 | | | PLEASE PROVIDE SYSTEM TO MEET ABOVE AND | | | DETAIL FOR WHAT WILL BE USED AND TIME OF | | | SCHEDULING. | | | | | | 2) NOTE: PLEASE CLARIFY THE TWO CIRCUITS | | | SHOWN IN PANEL FOR SD'S, YET THIS COULD | | | NOT BE LCOATED> | | | 215.5 | | | | | | 3) NOTE: PLEASE SUBMIT/ INDICATE THE AIC | | | RATINGS FOR ALL NEW SERVICE EQUIPMENT. | | | 110.9,215.5 | | | | | | 4) NOTE: PLEASE INDICATE THE EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO METERS | | | AND METER TO TENANT PANELS. PLEASE KNOW, | | | THE NUETRAL IN TENANT METER SHOULD BE | | | INDICATED WITH A "FLOATING NUETRAL". | | | PLEASE SEE 250.6,250.24B. | | | 250.110,250.122 | | | | | | 5) NOTE: PLEASE SEE PANELS BOTH INDICATE | | | SIGN CIRCUITS ,HOWEVER PLEASE SHOW | | | EITHER THE NEW OR EXISTING LOCATIONS ON | | | PLANS. | | | 600.5 | | | | | | | | | WHEN AND BEFORE RESUBMITTING PLANS, | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEET INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-04-11 00:00:00 | NOTES TO FOLLOW |
|