Plan Review Notes
Plan Review Notes For Permit 06030890
Permit Number 06030890
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE WE ARE UNDER THE
 2004 FBC. PLEASE SEE CHAPTER 13
 13-415.1.ABC.1.1 &.2
 PLEASE PROVIDE SYSTEM TO MEET ABOVE AND
 DETAIL FOR WHAT WILL BE USED AND TIME OF
 SCHEDULING.
  
 2) NOTE: PLEASE CLARIFY THE TWO CIRCUITS
 SHOWN IN PANEL FOR SD'S, YET THIS COULD
 NOT BE LCOATED>
 215.5
  
 3) NOTE: PLEASE SUBMIT/ INDICATE THE AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT.
 110.9,215.5
  
 4) NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO METERS
 AND METER TO TENANT PANELS. PLEASE KNOW,
 THE NUETRAL IN TENANT METER SHOULD BE
 INDICATED WITH A "FLOATING NUETRAL".
 PLEASE SEE 250.6,250.24B.
 250.110,250.122
  
 5) NOTE: PLEASE SEE PANELS BOTH INDICATE
 SIGN CIRCUITS ,HOWEVER PLEASE SHOW
 EITHER THE NEW OR EXISTING LOCATIONS ON
 PLANS.
 600.5
  
  
 WHEN AND BEFORE RESUBMITTING PLANS,
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEET INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-11 00:00:00NOTES TO FOLLOW