| 2006-03-18 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE THAT ALL PLANS SHALL |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLR FOR PLANS/ |
| | DESIGN. |
| | PLEASE SEE FBC 2004, ADIMINSTRATIVE CODE |
| | AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH. 106.3.4.3, 104.2.1 |
| | |
| | 2)NOTE: PLEASE SEE ALL OTHER SHEETS |
| | CONTAINING THE ENGINEERING FIRMM TITLE |
| | BLOCKS,; THESE ARE MISSING THE REQUIRED |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED PER FLORIDA ADMINISTRATIVE |
| | CODE, 61G15-23.002 ANDPER FLORIDA |
| | STATUES, 471.023 |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER ORNOT COMMENT IS |
| | MADE BY OTHER TRADES. |
| | |
| | 3)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | PER 210.52. |
| | THESE AHVE BEEN REDLINED ON PLANS. |
| | |
| | 4)NOTE: PLEASE SEE PLANS ARE MISSING |
| | PANEL "C' WHICH IS SHOWN ON RISER AND |
| | PANEL SCHEDULE, HOWEVER COULD NOT LOCATE |
| | THIS ON PLANS. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE CLARIFY PANEL "C" AS, |
| | PANEL "C" SHOWS 80A, YET PANEL "B" SHOWS |
| | 60A FEED? |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE KITCHEN ISLAND RECEPT |
| | TO BE SHOWN AS GFI PER 210.8A6 |
| | |
| | PLEASE COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT THE NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. ONLY ONE SET OF THE |
| | REMOVED OLD/VOIDED SHEETS ARE TO BE |
| | SUBMITTED BACK FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REIVEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |