| 2006-04-19 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS IF WORK IS NOT COMMENCED. |
| | NEED RE-RECORDED NOC. |
| | |
| | 2- PROVIDE DRAINAGE PLAN AS REQUIRED BY |
| | SEC. R401.3 2004 FLORIDA RES. CODE. |
| | |
| | 3- ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION IN TITLE BLOCK INCLUDING |
| | LICENSE # AND CERTIFICATE OF |
| | AUTHORIZATION FOR TREASURE COAST |
| | BUILDING ENGINEERS, INC. AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE AND FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002. |
| | |
| | 4- ENGINEER TO UPDATE ALL PLANS AND |
| | GENERAL NOTES TO COMPLY WITH 2004 |
| | FLORIDA RESIDENTIAL CODE AND 2004 |
| | FLORIDA BUILDING CODE WHICH ARE THE |
| | CODES IN EFFECT AFTER OCTOBER 1ST 2005. |
| | UPDATE ALL GENERAL NOTES AND SPECIFIC |
| | REFERENCE STANDARDS AND CURRENT EDITION |
| | ADOPTED BY THE 2004 CODES. SEE COMMENTS |
| | ON REVIEWED PLANS. |
| | |
| | 5- ROOF SHEATHING NAILING: REVISE SPECS |
| | SHOWN ON DETAILS AND NOTES THROUGHOUT |
| | ALL PLANS TO MATCH OR EXCEED MINIMUM |
| | FASTENING SPACING AS SHOWN ON TABLE |
| | 2304.9.1 OF FBC 2004. |
| | |
| | 6- WALL SECTIONS TO SPECIFY FIREBLOCKING |
| | MATERIAL AND SIZE AT CONCEALED SPACES AS |
| | REQUIRED BY SEC. R602.8 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 7- PROVIDE SPECIFICATIONS FOR DOOR |
| | INSIDE GARAGE TO COMPLY WITH SECTION |
| | R309.1 2004 RESIDENTIAL CODE. |
| | |
| | 8- ALL PRODUCT APPROVALS NEED TO BE |
| | APPROVED FOR 2004 FLORIDA CODE VERSION. |
| | RE-SUBMIT ALL FLORIDA OR LOCAL PRODUCT |
| | APPROVALS FOR: |
| | A) ENTRY DOORS. |
| | B) FRENCH DOORS MULLED TOGETHER AS |
| | SHOWN ON LIVING ROOM. |
| | ***NOTE: IF PRODUCT APPROVAL DOESN'T |
| | COVER 2 PAIR OF FRENCH DOORS MULLED |
| | TOGETHER, THEN, COMPLETE STRUCTURAL |
| | DETAILS AND SPECS ARE REQUIRED TO SHOW |
| | INSTALLATION. SEC. 106.1.2 OF CITY |
| | AMENDMENTS TO FBC 2004. |
| | C) POCKET SLIDING GLASS DOORS AS SHOWN |
| | ON PLANS BY LEISURE ROOM. |
| | D) ALL OTHER SLIDING GLASS DOORS. |
| | E) OVERHEAD GARAGE DOORS FOR LARGE AND |
| | SMALL DOORS. SEE PLANS. |
| | F) FIXED WINDOWS AS SHOWN ON PLANS. |
| | G) WINDOW MULLIONS. |
| | H) ALL STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS (SIMPSON AND USP. SEE PLANS) |
| | I) ROOF TILE. |
| | J) SINGLE HUNG WINDOWS. |
| | K) HORIZONTAL SLIDING WINDOWS AS SHOWN |
| | ON PLANS. |
| | L) GARAGE SIDE SWING DOOR. |
| | |
| | 9- STORM SHUTTERS: A) PROVIDE 2004 |
| | VERSION APPROVED FLORIDA OR LOCAL |
| | PRODUCT APPROVAL. |
| | B) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE THAT |
| | COVERS ALL REQUIRED MINIMUM INFORMATION |
| | FOR PLAN REVIEW. |
| | C) INFORMATION SUBMITTED IS FOR LOT |
| | 30. THIS IS LOT 22. REVISE AS REQUIRED. |
| | |
| | 10- UPDATE CONTRACTORS INFORMATION WITH |
| | PEMITING CLERK. NAME ON THE APPLICATION |
| | DOESN'T MATCH NAME SHOWN ON CONTRACTOR'S |
| | SCREEN. APPLICATION SAYS MONTICELLO |
| | HOMES, WHILE CONTRACTOR'S SCREEN SAYS AR |
| | CUSTOM HOMES. |
| | |
| | 11- ENERGY CALCULATIONS: A) CALCULATIONS |
| | NEED TO BE DONE FOR WORST CASE SCENARIO |
| | OR CALCULATED ACCORDING TO THE ACTUAL |
| | HOUSE ORIENTATION. CALCS SUBMITTED DON'T |
| | COMPLY WITH EITHER ONE. REVISE AS REQ'D. |
| | B) REVISE UNDER ATTIC AREA. NEED TO |
| | INCLUDE WALLS CONSIDERED AS CEILING AREA |
| | REQ'D BY SEC. 13-604.1.A.1 OF FBC 2004. |
| | C) COMPLETE INFORMATION ON TOP OF FORM |
| | INCLUDING CORRECT PROJECT NAME & ADDRESS |
| | |
| | 12- SOIL TEST REPORT NEEDS TO HAVE |
| | ENGINEER'S ORIGINAL SEAL AND SIGNATURE |
| | AS REQ'D BY CHAPTER 471 FLORIDA STATUTES |
| | |
| | 13- PROVIDE BBQ GRILL APPROVED LISTING |
| | AND SPECIFICATIONS THAT ALLOWS BBQ |
| | GRILLS TO BE INSTALLED IN THE REAR PORCH |
| | OR PROVIDE APPROVED LISTING AND SPECS |
| | FOR EXTERIOR USE HODD ABOVE BBQ GRILL. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | |
| | 14- OWES $1184.51 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 15- DETAIL 7 OF SHEET 4S1: SPECIFY |
| | SPACING FOR 2"X4" BLOCKING. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- DETAIL 4 OF SHEET 4S2: A) SPECIFY |
| | ALL FASTENERSINCLUDING ATTACHMENT OF |
| | "L" BRACE AT TOP AND BOTTOM. |
| | B) HOW LONG ARE THE ANCHOR BOLTS. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | C) HOW IS THE SIMPSON CONNECTOR HPAHD22 |
| | INSTALLED TO ALLOW THE 10" MIN. |
| | EMBEDMENT INTO THE U BLOCK BEAM. SEE |
| | SIMPSON CATALOGUE. |
| | |
| | 17- REVISE DETAIL 8 OF SHEET 4S2: SEE |
| | TABLE 2304.9.1 FBC 2004 FOR MINIMUM NAIL |
| | SPACING REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |