Plan Review Notes
Plan Review Notes For Permit 06030798
Permit Number 06030798
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00 
  
 DENIED
  
 1) SUBMIT PLAN OF WALLS TO BE REMOVED OR
 RELOCATED.
  
 2) SUBMIT LIST WITH DESCRIPTION OF WORK
 TO BE DONE
  
 3) NO TRADES ARE LISTED ON APPLICATION
 THEREFORE ANY WORK FOR ELECTRICAL,
 PLUMBING , ETC. TO BE UNDER SEPARATE
 PERMITS
  
 4) WITH REMOVAL OF FLOORING, PLACEMENT
 OF SOUND TRANSMISSION REDUCING MEMBRANE
 SHALL BE REQUIRED PER SECTION 1207 FBC
  
 5) WIND LOAD CRITERIA FOR COMPONANTS AND
 CLADDING SUCH AS DOORS AND WINDOWS SHALL
 BE DETERMINED BY AN ENGINEER FOR
 BUILDINGS OVER 60 FEET PERSECTION 1609
 FBC. THIS INFORMATION IS REQUIRED BEFORE
 PRODUCT APPROVALS CAN BE REVIEWED FOR
 COMPLIANCE
  
 6) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW