| Plan Review Notes For Permit 06030762 |
| Permit Number |
06030762 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-28 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING | | | INFORMATION RQUIRED FOR PLAN REVIEW: | | | | | | 1) COMPLY WITH FBC-2004 SEC 424.2 | | | PRIVATE SWIMMING POOLS.(ADD TO NOTES) | | | 2) FBC-2004 SEC 424.2.6.1 ENGINEERING | | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | ANSI/NSPI-5. (ADD TO NOTES) | | | 3) PIPING SCHEMATIC SHOWS AN 1-1/2" | | | VENT, THE VENT PIPE MAXIMUM | | | LENGTH CHART IS FOR 1" VENTS, AND THE | | | MAIN DRAIN DETAIL INDCATES A 1" VENT. | | | THESE THREE DETAILS NEED TO CORRELATE TO | | | EITHER 1" OR 1-1/2". | | | 10) FBC-2004 424.2.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK.(ADD TO DETAIL) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | |
|