Plan Review Notes
Plan Review Notes For Permit 06030758
Permit Number 06030758
Review Stop B
Sequence Number 2
Notes
Date Text
2006-03-30 00:00:00DENIED
  
 1) FLORIDA COVER SHEET DOES NOT IS FOR A
 MODIFIED BITUMEN ROOF SYSTEM AND THE NOA
 IS FOR A POLYSTICK UNDERLAYMENT. THESE
 ARE TWO DIFFERENT SYSTEMS.
  
 2) THE POLYSTICK UNDERLAYMENT CAN NOT BE
 LEFT EXPOSED MORE THAN 90 DAYS. READ
 LIMITATION NUMBER 6 ON PAGE 4 OF THE
 NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  