| 2007-05-09 16:58:20 | |
| | |
| | REVISION DENIED |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL.THE ADDITION OF THE |
| | ELEVATOR, MDP-3 SERVICE ANDRELATED EQUIPMENT, 2000 |
| | AMP QUICK DISCONNECT SWITCHBOARD, THE FEEDER AND BRANCH |
| | CIRCUITING FOR EQUIPMENT IN THE CARPENTER SHOP, METAL |
| | SHOP, PAINT SHOP, SANDING AREA ETC. THAT ARE ADDED IN |
| | THIS REVISION REQUIRE THE VALUE TO BE INCREASED. ADJUST |
| | THE VALUE AT THE PERMIT CLERKS DESK, AND PAY THE |
| | DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | 2}IDENTIFICATION IS REQUIRED AT MDP-3, AS IS SHOWN AT |
| | MSB-5 PER 230.2(E). PLEASE ADD TO THE PLAN. SHEET |
| | E3.2. |
| | |
| | 3} MDP-1, MDP-2 AND MSB5 REQUIRE GROUND FAULT |
| | PROTECTION PER 230.95 AND 240.13. PLEASE INDICATE ON |
| | PLANS AT THE PANEL SCHEDULES. |
| | |
| | 4} INDICATE COMPLIANCE WITH CHAPTER 13 FBC. PLACE ALL |
| | RELATED EQUIPMENT ON THE PLAN, PROVIDE A LEGENDFOR |
| | SAME. SUBMIT NEW ENERGY CALCULATIONS CORRELATING WITH |
| | ALL FIXTURE TYPES INDICATED ON THE DRAWINGS. |
| | |
| | 5} PLEASE SEE CIRCUITS LABLED P5-4, P5-17,19, P5- 21,23 |
| | ANDP5-32 ARE MISMARKED. (THOSE CIRCUITS ARE LISTED IN |
| | PANEL B5). |
| | |
| | 6} PLEASE INDICATE THE DUTY-CYCLE SERVICE OF THE 25 HP |
| | ELEVATOR MOTOR. VERIFY THAT THERE IS A 400 AMP FUSED |
| | DISCONNECT ON THE LOAD SIDE OF A 225 AMP DISCONNECT. |
| | SHEET E4.5, MSB5 RISER. |
| | |
| | 7} PANEL HB4 FEEDER IS 250 AMPS PER THE FEEDER |
| | SCHEDULE, LISTED AS 225 AMP ON THE RISER (SHEET E4.5), |
| | AND LISTED AS 400 AMPS ON THE PANEL SCHEDULE SHEET |
| | E4.7. CORRELATE SAME. |
| | |
| | 8} PLEASE VERIFY OR REMOVE THE NOTE UNDER MSB5, SHEET |
| | E4.1, REGARDING THE 6' WIDTH. |
| | |
| | 9} PLEASE INDICATE THEDESIGNERS INTENDED |
| | CLASSIFICATION OF THE CARPENTER SHOP. NOT KNOWINGTHE |
| | TYPE OF DUST COLLECTION SYSTEM TO BE INSTALLED, THE |
| | REVIEWER CANNOT DETERMINE THAT CLASSIFICATION AT THIS |
| | TIME.PER 500.5. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |