| Date |
Text |
| 2007-03-28 12:22:37 | |
| | |
| | DENIED/CONFLICTING INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CHANGES ON THE PLANS FOR |
| | CLARITY. |
| | |
| | 1} E.2.1 THE SHEET SUBMITTED FOR REVISION DOES NOT THE |
| | CONTAIN THE SAME FLOOR PLANS AS THE SHEET IN THE PERMIT |
| | SET IT IS INTENDED TO REPLACE.ALSO PLEASE NOTE |
| | "REVISION #3 DATED 9/1/06 AND THE DELTA NUMBERED THE |
| | SAME IN THE BLOCK WITH THE SHEET NUMBER, IS A DATE |
| | PRIOR TO THE PERMIT SET DATE. SINCE ALL SHEETS |
| | SUBMITTED DO NOT MATCH THE PERMIT SET, POSSIBLY THE |
| | WRONG SET WAS SUBMITTED. |
| | |
| | 2} E2.2, NOT THE SAME FLOOR PLANS AS PERMIT SET. ALSO |
| | THE "COVERED WORKSHED" AND STORAGE SHED HAVE BEEN |
| | REMOVED WITH OUT CLOUDING OR OTHER INDICATION THEY WERE |
| | INTENTIONALLY REMOVED. |
| | |
| | 3} E2.3, THIS SHEET CONTAINS NO POWER OR SYSTEMS PLAN |
| | AS THE SHEET IT IS INTENDED TO REPLACE DOES. |
| | |
| | 4} E2.4, THE REVISION IS SHOWING 2ND FLOOR LIGHTING, |
| | THE PERMIT SET IS 1ST FLOOR PLANS. |
| | |
| | 5} E3.1 OF THE PERMIT SET IS THE RISER AND FEEDER |
| | SCHEDULES AND CANNOT BE REVISED WITH A FLOOR PLAN |
| | DRAWING. ALSO THE REVISED SHEET SHOWS A "GENERATOR |
| | QUICK DISCONNECT" SWITCHBOARD AT THE RELOCATED |
| | MSB.PLEASE SUBMIT SPECIFICATIONS FOR THIS AND ADD TO |
| | THE RISER TO INDICATE LOCATION IN THE SERVICE SYSTEM. |
| | |
| | 6} E3.2, REVISION CANNOT REPLACE THE RISER ON THE |
| | PERMIT SET. |
| | |
| | 7} E4.1 AND E4.2 DO NOT CORRELATE TO THE PANELS ON THE |
| | PERMITTED SHEETS. THEY CONTAIN SCHEDULES NOT ON PERMIT |
| | SET AND OMIT SCHEDULES CONTAINED ON THE PERMIT SET. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |