2007-03-28 12:22:37 
  
 DENIED/CONFLICTING INFORMATION
  
 PLEASE MAKE THE FOLLOWING CHANGES ON THE PLANS FOR
 CLARITY.
  
 1} E.2.1 THE SHEET SUBMITTED FOR REVISION DOES NOT THE
 CONTAIN THE SAME FLOOR PLANS AS THE SHEET IN THE PERMIT
 SET IT IS INTENDED TO REPLACE.ALSO PLEASE NOTE
 "REVISION #3 DATED 9/1/06 AND THE DELTA NUMBERED THE
 SAME IN THE BLOCK WITH THE SHEET NUMBER, IS A DATE
 PRIOR TO THE PERMIT SET DATE. SINCE ALL SHEETS
 SUBMITTED DO NOT MATCH THE PERMIT SET, POSSIBLY THE
 WRONG SET WAS SUBMITTED.
  
 2} E2.2, NOT THE SAME FLOOR PLANS AS PERMIT SET. ALSO
 THE "COVERED WORKSHED" AND STORAGE SHED HAVE BEEN
 REMOVED WITH OUT CLOUDING OR OTHER INDICATION THEY WERE
 INTENTIONALLY REMOVED.
  
 3} E2.3, THIS SHEET CONTAINS NO POWER OR SYSTEMS PLAN
 AS THE SHEET IT IS INTENDED TO REPLACE DOES.
  
 4} E2.4, THE REVISION IS SHOWING 2ND FLOOR LIGHTING,
 THE PERMIT SET IS 1ST FLOOR PLANS.
  
 5} E3.1 OF THE PERMIT SET IS THE RISER AND FEEDER
 SCHEDULES AND CANNOT BE REVISED WITH A FLOOR PLAN
 DRAWING. ALSO THE REVISED SHEET SHOWS A "GENERATOR
 QUICK DISCONNECT" SWITCHBOARD AT THE RELOCATED
 MSB.PLEASE SUBMIT SPECIFICATIONS FOR THIS AND ADD TO
 THE RISER TO INDICATE LOCATION IN THE SERVICE SYSTEM.
  
 6} E3.2, REVISION CANNOT REPLACE THE RISER ON THE
 PERMIT SET.
  
 7} E4.1 AND E4.2 DO NOT CORRELATE TO THE PANELS ON THE
 PERMITTED SHEETS. THEY CONTAIN SCHEDULES NOT ON PERMIT
 SET AND OMIT SCHEDULES CONTAINED ON THE PERMIT SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  