2007-02-21 16:33:25 
 SWITCHGEAR SUBMITTAL NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE SUBMITTAL FOR SWITCHBOARD MSB5 SHOWS IT BEING
 LARGER THAN THE 6' MAXIMUM ALLOWED FOR THE ROOM IN
 WHICH IT'S DESIGNATED TO BE INSTALLED, WHICH DOES NOT
 CONFORM TO110.26(C)(2),"ENTRANCE--- AT EACH END" ALSO
 WITH FRONT AND LEFT ACCESS REQUIRED, IT WILL NOT ALLOW
 WORKING SPACE AT THE END OF THE GEAR.
  
 I AM RETURNING BOTH FULL SETS OF SUBMITTALS CONTAINING
 THE SWITCHBOARD INFORMATION FOR CORRECTION OF MSB5.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER