| 2007-04-10 10:32:26 | BUILDING PLAN REVIEW |
| | PERMIT: 06030729 |
| | ADD: 4200 N. FLAGLER DR |
| | CONT: CENTEX |
| | TEL: (954)605-1010 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISIONREVIEW |
| | ACTION: DENIED |
| | |
| | THIS REVISION # 4 IN CREATING A TRUE SECOND STORY WILL |
| | NEED THREE AREAS TO BE CORRECTED BEFORE THE REVIEW |
| | PROCESS CAN BE COMPLETED. |
| | 1) IN CREATINF A TRUE SECOND STORY THE BUILDING CODE |
| | ANALYSIS NEEDS TO BE CORRECTED. CHANGE NUMBER 5 HAS |
| | CRETED A SECOND STORY BUT THE AREA |
| | INCREASES TAKEN ARE FOR A SINGLE STORY BUILDING. A 200% |
| | INCREASE CAN BE TAKEN FOR MULTIPLE STORY BUILDINGS ( |
| | 506.3) NOT THE 300%. THE DESIGNERS HAVEN'T SHOWN |
| | ANY FRONTAGE INCEASES AAS LISTED UNDER 506.2. PLEASE |
| | CORRECT, SHOW CALCULATIONS. |
| | |
| | 2) NUMBER TWO IS AN EITHER OR SITUATION, THE NEW |
| | OFFICES OVER THE PAINT SHOP WILL REQUIRE EXITS, SHEET |
| | A-2.05 INDICATES THE TWO EXITS IN A HASHED LINE GOING |
| | TO THE ENCLOSED EXITS GOING TO THE OPPOSITE ENDS OF |
| | THIS PORTION OF THE BUILDING. |
| | 2A) SITUATION # 1- WITH THE SCENARIOLISTED ABOVE, THE |
| | CODE REQUIRES TWO EXITS TABLE 1018.2 LIMITS THE TRAVEL |
| | TO 75 FEET FOR A SINGLE EXIT. FOR SPRINKLERED BUILDINGS |
| | THE EXIT ACCESS TRAVEL DISTANCE IS MOST RESTRICTIVE AT |
| | 250' FOR AN F1 OCCUPANCY, THE DESIGN DOES COMPLY WITH |
| | THIS REQUIREMENT. PLEASE INDICATE THE 36" PATH OF |
| | TRAVEL ON THE PLAN. THE SITUATION THAT OCCURS WHEN THE |
| | OCCUPANT LOAD OF THE NEWLY CREATED SECOND FLOOR |
| | BUSINESS |
| | 27 OCCUPANT LOAD/ 2 = 13.5 OR 14 OCCUPANTS PER EXIT |
| | PLUS THE MEZANINE OCCUPANTS(6) WILL EQUAL 20 OCCUPANTS |
| | THAT WILL CROSS THE AREA THAT IS OPEN TO BELOW IN THE |
| | PARTS DEPARTMENT. THE SECTION ON THE OPENNESS OF |
| | MEZZANINES 505.4(2) AT LEAST ONE DIRECT ACCESS TO AN |
| | EXIT FROM THE MEZZANINE. THE AREA THAT IS OPEN TO THE |
| | PARTS DEPARTMENT WOULD HAVE TO BE ENCLOSED. NEITHER THE |
| | ENCLOSED MEZZANINE AREAS NEED TO BE FIRE RATED NOR THE |
| | ACCESS CORRIDOR DUE TO THE FIRE SPRINKLERS. IF THIS |
| | SITUATION IS DESIRED TWO ISSUES NEED TO BE CORRECTED |
| | A) THE STAIRWAY THAT LEADS FROM THE BUSINESS OFFICE TO |
| | THEPAINT SHOP WOULD NEED TO HAVE THE EXIT SIGN |
| | REMOVED SINCE THIS EXIT LEADS INTO A MORE DANGEROUS |
| | OCCUPANCY AND NOT DIRECTLY TO THE EXTERIOR. |
| | B) ENCLOSE THAT PORTION OF WALL IN THE PARTS MEZZANINE |
| | LEVEL. IF THIS SITATION IS DECIDED TO BE USED ON SHEET |
| | E-2.3 THE EGRESS LIGHT WOULD NEED TO BE REMOVED FROM |
| | THIS STAIRWAY. THE STAIRWAY NEXT TO THE CONTAINMENT BAY |
| | WOULD NEED TO BE 1 HR FIRE RATED AS WELL AS THE |
| | RESTROOM BELOW1019.1.5. THE OTHER ISSUE WILL BE THE |
| | EXTERIOR WALL OF THIS STARWELL WHICH WOULS NOT NORMALLY |
| | NEED TO BE RATED WILL NEED TO BE RATED BECAUSE OF THE |
| | CLOSENESS OF THE CONTAINMENT TANK, RESTROOM EXHAUST FAN |
| | INDICATES PENETRATING THIS WALL REQUIRING A FIRE |
| | DAMPER. |
| | |
| | SITUATION # 2- IF THE PORTION OF THE MEZZANINE IN THE |
| | PARTS ROOM IS TO REMAIN OPEN, THEN THE OCCUPANT LOAD |
| | FROM THE BUSINESS OCCUPANCY CAN'T CROSS THIS PORTION OF |
| | OPEN MEZZANIN AND THE STAIRWELL NEXT TO THE BUSINESS |
| | OCCUPANCY WILL NEED TO BE 1 HR FIRE RATED, WITH A NEW |
| | DOORWAY BEING CREATED SO THE EXIT DISCHARGE FROM THE |
| | STAIRS WILL LEAD DIRECTLY TO THE EXTERIOR WITHOUT GOING |
| | THROUGH THE PAINT SHOP A MORE DANGERIOUS OCCUPANCY. |
| | GROUP. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |