| 2007-03-12 15:42:02 | -------------DENIED----------------- |
| | |
| | 1. PG M2.1 NOTE #3: FLAME SPREAD OF 25 OR LESS IS |
| | REQUIRED IN PLENUMS PER FBC,M 602.2.1. PLAN STATES A |
| | FLAME SPREAD OF 250 IS ACCEPTABLE. PLEASE CORRECT AND |
| | RESUBMIT. |
| | |
| | 2. PG M2.1 - EF1 & EF2 ARE BOTH LOCATE IN A PLENUM |
| | CEILING AREA, CAUSING DOWNSTREAM DUCTS UNDER POSITIVE |
| | PRESSURE TO ALSO BE LOCATED IN A PLENUM. EXHAUST DUCTS |
| | UNDER POSITIVE PRESSURE SHALL NOT BE LOCATED IN A |
| | RETURN AIR PLENUM PER FBC,M 601.3. |
| | |
| | 3. PG M2.1 - EF1 IN BATHROOM UNDER RATED VERTICAL EXIT |
| | ACCESS (STAIRWAY). THE EXHAUST DUCT WILL BE PENETRATING |
| | ONE OR MORE RATED ASEMBLIES (SEE FBC 1019.1.5). THESE |
| | OPENINGS SHALL BE PROTECTED PER FBC,M 607.5. |
| | |
| | 4. PG M2.3 & M2.4 PLAN SHOWS SUPPLY AIR DUCTS ENTERING |
| | STAIR SERVING AS VERTICAL EXIT ENCLOSURES. THESE |
| | OPENINGS ARE PROHIBITED PER FBC 1019.1.2. |
| | |
| | 5. A2.03 SHOWS A RATED WALL SEPARATING SPACES (SEE COL. |
| | LINE 16) WHICH IS NOT SHOWN ON MECHANICAL REVISIONS. IF |
| | PARTITIONS AND/OR RATED ASSEMBLIES WHICH ARE NOT SHOWN |
| | ON MECHANICAL DRAWINGS ARE INSTALLED, THEY WILL IMPACT |
| | THE MECHANICAL SYSTEM. A COMPLETE REVIEW OF THESE PAGES |
| | CAN NOT BE DONE AT THIS TIME. PLEASE REVISE DRAWINS SO |
| | THAT MECHANICAL AND ARCHITECTURAL PLANS CORRELATE SO A |
| | COMPLETE REVIEW CAN BE PERFORMED. FBC 106.1.1. |
| | |
| | |