Plan Review Notes
Plan Review Notes For Permit 06030729
Permit Number 06030729
Review Stop M
Sequence Number 3
Notes
Date Text
2007-03-12 15:42:02-------------DENIED-----------------
  
 1. PG M2.1 NOTE #3: FLAME SPREAD OF 25 OR LESS IS
 REQUIRED IN PLENUMS PER FBC,M 602.2.1. PLAN STATES A
 FLAME SPREAD OF 250 IS ACCEPTABLE. PLEASE CORRECT AND
 RESUBMIT.
  
 2. PG M2.1 - EF1 & EF2 ARE BOTH LOCATE IN A PLENUM
 CEILING AREA, CAUSING DOWNSTREAM DUCTS UNDER POSITIVE
 PRESSURE TO ALSO BE LOCATED IN A PLENUM. EXHAUST DUCTS
 UNDER POSITIVE PRESSURE SHALL NOT BE LOCATED IN A
 RETURN AIR PLENUM PER FBC,M 601.3.
  
 3. PG M2.1 - EF1 IN BATHROOM UNDER RATED VERTICAL EXIT
 ACCESS (STAIRWAY). THE EXHAUST DUCT WILL BE PENETRATING
 ONE OR MORE RATED ASEMBLIES (SEE FBC 1019.1.5). THESE
 OPENINGS SHALL BE PROTECTED PER FBC,M 607.5.
  
 4. PG M2.3 & M2.4 PLAN SHOWS SUPPLY AIR DUCTS ENTERING
 STAIR SERVING AS VERTICAL EXIT ENCLOSURES. THESE
 OPENINGS ARE PROHIBITED PER FBC 1019.1.2.
  
 5. A2.03 SHOWS A RATED WALL SEPARATING SPACES (SEE COL.
 LINE 16) WHICH IS NOT SHOWN ON MECHANICAL REVISIONS. IF
 PARTITIONS AND/OR RATED ASSEMBLIES WHICH ARE NOT SHOWN
 ON MECHANICAL DRAWINGS ARE INSTALLED, THEY WILL IMPACT
 THE MECHANICAL SYSTEM. A COMPLETE REVIEW OF THESE PAGES
 CAN NOT BE DONE AT THIS TIME. PLEASE REVISE DRAWINS SO
 THAT MECHANICAL AND ARCHITECTURAL PLANS CORRELATE SO A
 COMPLETE REVIEW CAN BE PERFORMED. FBC 106.1.1.
  
  