| Plan Review Notes For Permit 06030729 |
| Permit Number |
06030729 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-10 14:49:29 | PROVISO: | | | | | | SMOKE DETECTORS ARE REQUIRED IN SUPPLY AIR SYSTEMS WITH | | | A DESIGN CAPACITY GREATER THAN 2,000 CFM, PER 2004 FMC | | | 606.2.1.PLEASE NOTE, AHU SYSTEM 1 INDICATES A 5 TON | | | SYSTEM WHICH MAY HAVE THE CAPACITY TO PRODUCE GREATER | | | THAN 2,000 CFM.PLEASE VERIFY WITH MANUFACTURER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. | | 2006-10-10 13:01:53 | |
|