| 2006-09-26 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW COMPLIANCE WITH CHAPTER | | | 13, ENERGY CODE, SECTIONS 413,414 AND | | | 415 FOR LIGHTING CONTROLS. INDICATE | | | LOCATION OF EQUUIPMENT AND DEVICES SUCH | | | AS TIME CLOCKS AND OCCUPANCY SENSORS ON | | | THE PLAN. | | | | | | 2} MDP2 IS LISTED AS A MLO ON THE PLAN. | | | PLEASE CORRECT OR SHOW COMPLIANCE WITH | | | 230.71. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|