| 2006-09-18 00:00:00 | PERMIT: 06030729 |
| | ADD:4300 N FLAGLER DR |
| | CONT: ROONEY CENTEX CONSTRUCTION |
| | TEL: (561)478-0381 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * 2004 WEST PALM BEACH AMENDMENTS |
| | CHAPTER 1 OF FBC |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | -----NOTE----- |
| | |
| | THIS PERMIT APPLICATION IS FOR THE MTC |
| | (MARINE TECHNOLOGIES CENTER) BUILDING. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2)BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, |
| | DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 3)BUILDING PROVISO: 109.3.10.1 HURICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) PLANSCOMPLIED WITH THE DEFINITION |
| | OF MEZZANINE THERE ARE OTHER CODE ISSUE |
| | THAT WILL NEED TO BE ADDRESSED: |
| | 6A) PLEASE PROVIDE INFORMATION HOW |
| | VERTICAL ACCESSIBILITY WILL BE |
| | ADDRESSED. PROVIDE DOCUMENTATION. |
| | |
| | 6B)2ND REQUEST, PLEASE SEE 110.4.2 |
| | STORAGE & FACTORY- INDUSTRIAL |
| | OCCUPANCIES. IT SHALL BE THE |
| | RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPIETOR OR OCCUPANT OF GROUP S AND |
| | GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| | WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| | TO OCCUR, TO EMPLOY A COMPETENT ARCHI- |
| | TECT OR ENGINEER IN COMPUTING THE SAFE |
| | FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- |
| | TIONS SHALL BE ACCOMPANIED BY AN AFFA- |
| | DAVIT FROM THE ARCHITECT OR ENGINEER |
| | STATING THE SAFE ALLOWABLE FLOOR LOADS |
| | ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| | COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| | AS A PERMANENT RECORD OF THE BLDG DEPT. |
| | RESPONCE: PLEAASE SEE AFFIDAVIT AND |
| | COMPUTATIONS FOR SAFE ALLOWABLE FLOOR |
| | LOAD CAPACITY. (BUTLER TO PROVIDE) |
| | |
| | NO AFFADAVIT OR CALCULATIONS WERE |
| | SUBMITTED. CUT SECTION DO6-137731-02B |
| | DOES INDICATE MEZZANINE LEVEL BUT NO |
| | FLOOR LOADS. I ALSO CHECKED COLUMNS FOR |
| | POINT LOADING. |
| | |
| | 6C) 2ND REQUEST, 10.4.3.SIGNS REQUIRED. |
| | IN EVERY |
| | BUILDING OR PART OF A BUILDING USED FOR |
| | STORAGE, INDUSTRIAL OR HAZARDOUS PUR- |
| | POSES, THE SAFE FLOOR LOADS, AS REVIEWED |
| | BY THE BUILDING OFFICIAL ON THE PLAN, |
| | SHALL BE MARKED ON PLATES OF APPROVED DE |
| | SIGN WHICH SHALL BE SUPPLIED & SECURELY |
| | AFFIXED BY THE OWNER OF THE BUILDING IN |
| | A CONSPICUOUS PLACE IN EACH STORY TO |
| | WHICH THEY RELATE. SUCH PLATES SHALL NOT |
| | BE REMOVEDOR DEFACED, & IF LOST, |
| | REMOVED THE OWNER OF THE BUILDING SHALL |
| | REPLACE THEM. |
| | |
| | THE SIGNAGE HAS TO CORRALATE WITH THE |
| | DESIGN FLOOR LOAD FOR THE MEZZANINE: |
| | 125 LBS/ SQ FT LIGHT |
| | 250 LBS/ SQ FT HEAVY |
| | |
| | 7) 2ND REQUEST, THE SECOND FLOOR OFFICE |
| | AREA HOW MANY |
| | PEOPLE WILL OCCUPY THIS AREA? WILL THERE |
| | BE ANY STORAGE AREAS ON THE SECOND |
| | FLOOR? POSSIBLE VERTICAL ACCESSABILITY. |
| | PROVIDE DETAILS HOW VERTICAL |
| | ACCESSBILITY WILL BE MET. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) 2ND REQUEST, ) PROVIDE INFORMATION |
| | WHY THERE IS A CONTAINMENT AREA, BAY# 8? |
| | THE RESPONSE IS : PLEASE SEE ATTACHED |
| | LETTER OF THE PURPOSE OF THE CONTAINMENT RYBOVICH). |
| | THERE IS NO LETTER OR OTHER DOCUMENTATION ATTACHED TO |
| | THESE REVIEW |
| | COMMENTS! |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) COMPLIED THROUGH FOUNDATION PERMIT |
| | ELEVATION CERTIFICATE. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPLIED. |
| | |
| | 17) BUTLER LAYOUT SHEETS 2 OF THE 3 |
| | SEEETS HAVE RAISED SEALS THE OTHER IS |
| | MISSING THE RAISED SEAL. FAC |
| | 61G15-23.002 (FROM FOUNDATION SET, NO |
| | PLANS FOUND IN THE BLDG SET). |
| | MISSING THE BUTLER LAYOUT SHEETS ALL |
| | TOGETHER. |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) 2ND REQUEST, W P B ADMINISTRTIVE |
| | CODE 106.3.3* PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL |
| | APPROVAL. |
| | |
| | 22) COMPLIED. |
| | |
| | 23) COMPLIED. |
| | |
| | 24) 2ND REQUEST,THE PERMIT APPLICATION |
| | STATES DESCRIPTION OF WORK TO BE A 1 |
| | STORY MTC PRE-ENGINEERED BUILDING. NO |
| | OTHER IMPROVEMENTS ARE MENTIONED UNDER |
| | THE PREMIT APPLICATION DESRIPTION OF |
| | WORK. THE PLANS SUBMITTED HAVE AN |
| | ELECTRICAL GEAR BUILDING WITH ARCH M-E-P |
| | AND STRUCTURAL PLANS INCLUDED. NOT TO BE |
| | PART OF THIS PERMIT, NOR IS SITE |
| | IMPROVEMETNS. |
| | |
| | THE RESPONSE INDICATES , YES THE |
| | ELECTRICAL GEAR ROOM IS TO BE PART OF |
| | THIS PERMIT APPLICATION, PLEASE ADD TO |
| | THE PROJECT DESCRIPTION. |
| | |
| | THE PERMIT APPLICATION NOT SUBMITTED. |
| | |
| | |
| | 25) 2ND REQUEST, A-6.01 INDICATES A |
| | DETAIL 2/A-6.02 WHICH INDICATES USE OF |
| | FOAM TRIM. 1406.2.2 ARCHITECTURAL TRIM. ARCHITECTURAL |
| | TRIM THAT EXCEEDS 40 FEET |
| | (12 192 MM) IN HEIGHT ABOVE GRADE PLANE |
| | SHALL BE CONSTRUCTED OF APPROVED |
| | NONCOMBUSTIBLE MATERIALS AND SHALL BE |
| | SECURED TO THE WALL WITH METAL OR OTHER |
| | APPROVED NONCOMBUSTIBLE BRACKETS. |
| | |
| | IF YOU DO NOT AGREE WITH THE BUILDING |
| | OFFICIALS DECISION AND OR INTERPRETATION |
| | OF THE CODE YOU MAY APPLY FOR AN |
| | APPEAL TO THE CONSTRUCTION BOARD OF |
| | ADJUSTMENT & APPEAL, OR YOU MAY APPLY |
| | FOR A VARIANCE TO THE TECHNICAL CODES. |
| | ACOPY OF THE FORM IS ATTACHED. |
| | |
| | 26) 2ND REQUEST,BEFORE A PERMIT TO |
| | CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |