Notes
Date Text
2006-09-18 00:00:00PERMIT: 06030729
 ADD:4300 N FLAGLER DR
 CONT: ROONEY CENTEX CONSTRUCTION
 TEL: (561)478-0381
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * 2004 WEST PALM BEACH AMENDMENTS
 CHAPTER 1 OF FBC
  
 2ND REVIEW
 ACTION: DENIED
  
 -----NOTE-----
  
 THIS PERMIT APPLICATION IS FOR THE MTC
 (MARINE TECHNOLOGIES CENTER) BUILDING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3)BUILDING PROVISO: 109.3.10.1 HURICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) PLANSCOMPLIED WITH THE DEFINITION
 OF MEZZANINE THERE ARE OTHER CODE ISSUE
 THAT WILL NEED TO BE ADDRESSED:
 6A) PLEASE PROVIDE INFORMATION HOW
 VERTICAL ACCESSIBILITY WILL BE
 ADDRESSED. PROVIDE DOCUMENTATION.
  
 6B)2ND REQUEST, PLEASE SEE 110.4.2
 STORAGE & FACTORY- INDUSTRIAL
 OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 RESPONCE: PLEAASE SEE AFFIDAVIT AND
 COMPUTATIONS FOR SAFE ALLOWABLE FLOOR
 LOAD CAPACITY. (BUTLER TO PROVIDE)
  
 NO AFFADAVIT OR CALCULATIONS WERE
 SUBMITTED. CUT SECTION DO6-137731-02B
 DOES INDICATE MEZZANINE LEVEL BUT NO
 FLOOR LOADS. I ALSO CHECKED COLUMNS FOR
 POINT LOADING.
  
 6C) 2ND REQUEST, 10.4.3.SIGNS REQUIRED.
 IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 THE SIGNAGE HAS TO CORRALATE WITH THE
 DESIGN FLOOR LOAD FOR THE MEZZANINE:
 125 LBS/ SQ FT LIGHT
 250 LBS/ SQ FT HEAVY
  
 7) 2ND REQUEST, THE SECOND FLOOR OFFICE
 AREA HOW MANY
 PEOPLE WILL OCCUPY THIS AREA? WILL THERE
 BE ANY STORAGE AREAS ON THE SECOND
 FLOOR? POSSIBLE VERTICAL ACCESSABILITY.
 PROVIDE DETAILS HOW VERTICAL
 ACCESSBILITY WILL BE MET.
  
 8) COMPLIED.
  
 9) 2ND REQUEST, ) PROVIDE INFORMATION
 WHY THERE IS A CONTAINMENT AREA, BAY# 8?
 THE RESPONSE IS : PLEASE SEE ATTACHED
 LETTER OF THE PURPOSE OF THE CONTAINMENT RYBOVICH).
 THERE IS NO LETTER OR OTHER DOCUMENTATION ATTACHED TO
 THESE REVIEW
 COMMENTS!
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED THROUGH FOUNDATION PERMIT
 ELEVATION CERTIFICATE.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) BUTLER LAYOUT SHEETS 2 OF THE 3
 SEEETS HAVE RAISED SEALS THE OTHER IS
 MISSING THE RAISED SEAL. FAC
 61G15-23.002 (FROM FOUNDATION SET, NO
 PLANS FOUND IN THE BLDG SET).
 MISSING THE BUTLER LAYOUT SHEETS ALL
 TOGETHER.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) 2ND REQUEST, W P B ADMINISTRTIVE
 CODE 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL
 APPROVAL.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) 2ND REQUEST,THE PERMIT APPLICATION
 STATES DESCRIPTION OF WORK TO BE A 1
 STORY MTC PRE-ENGINEERED BUILDING. NO
 OTHER IMPROVEMENTS ARE MENTIONED UNDER
 THE PREMIT APPLICATION DESRIPTION OF
 WORK. THE PLANS SUBMITTED HAVE AN
 ELECTRICAL GEAR BUILDING WITH ARCH M-E-P
 AND STRUCTURAL PLANS INCLUDED. NOT TO BE
 PART OF THIS PERMIT, NOR IS SITE
 IMPROVEMETNS.
  
 THE RESPONSE INDICATES , YES THE
 ELECTRICAL GEAR ROOM IS TO BE PART OF
 THIS PERMIT APPLICATION, PLEASE ADD TO
 THE PROJECT DESCRIPTION.
  
 THE PERMIT APPLICATION NOT SUBMITTED.
  
  
 25) 2ND REQUEST, A-6.01 INDICATES A
 DETAIL 2/A-6.02 WHICH INDICATES USE OF
 FOAM TRIM. 1406.2.2 ARCHITECTURAL TRIM. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 IF YOU DO NOT AGREE WITH THE BUILDING
 OFFICIALS DECISION AND OR INTERPRETATION
 OF THE CODE YOU MAY APPLY FOR AN
 APPEAL TO THE CONSTRUCTION BOARD OF
 ADJUSTMENT & APPEAL, OR YOU MAY APPLY
 FOR A VARIANCE TO THE TECHNICAL CODES.
 ACOPY OF THE FORM IS ATTACHED.
  
 26) 2ND REQUEST,BEFORE A PERMIT TO
 CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026