| Plan Review Notes For Permit 06030729 |
| Permit Number |
06030729 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-26 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE. | | | | | | 1.PLEASE PROVIDE INFORMATION AS TO | | | WHAT TYOE IF WORK WILL BE PERFORMED IN | | | THE DIFFERENT BAY'S. | | | | | | 2.PROVIDE MSDS SHEETS FOR ANY | | | HAZARDOUS LIQUIDS AND MATERIALS. | | | | | | 3.THE FOLLOWING FANS ARE LOCATED OVER | | | DOOR EXITS, BAY 12, 10, 3, 5, 7, & 14. | | | PLEASE NOTE, PER 2004 FMC 401.5.2, | | | IYTDIIR EXHAUST OPENINGS SHALL NOT BE | | | DIRECTED ONTO WALKWAYS AND SHALL BE | | | LOCATED AS NOT TO CREATE A NUISANCE. | | | | | | 4.TEF2 IS ALSO TERMINATING OVER A | | | DOOR. | | | | | | 5.HAZARDOUS EXHAUST SYSTEMS SHALL | | | COMPLY WITH 2004 FMC 510. | | | | | | 6.PLEASE PROVIDE ENERGY & SIZING | | | CALCULATIONS IN ACCORDANCE WITH 2004 FBC | | | CHAPTER 13, SECTION 13-400.0.ABC AND | | | 13-407.1ABC.1. | | | | | | 7.PLEASE PROVIDE FLOOD ELEVATION | | | CERTFICATE.PLEASE NOTE, THE CITY CODE | | | REQUIRES AND ADDITIONAL 6" TO THE | | | FEDERAL STANDARD. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|