2006-06-26 00:00:00DENIED:2004 FLORIDA BUILDING CODE.
  
 1.PLEASE PROVIDE INFORMATION AS TO
 WHAT TYOE IF WORK WILL BE PERFORMED IN
 THE DIFFERENT BAY'S.
  
 2.PROVIDE MSDS SHEETS FOR ANY
 HAZARDOUS LIQUIDS AND MATERIALS.
  
 3.THE FOLLOWING FANS ARE LOCATED OVER
 DOOR EXITS, BAY 12, 10, 3, 5, 7, & 14.
 PLEASE NOTE, PER 2004 FMC 401.5.2,
 IYTDIIR EXHAUST OPENINGS SHALL NOT BE
 DIRECTED ONTO WALKWAYS AND SHALL BE
 LOCATED AS NOT TO CREATE A NUISANCE.
  
 4.TEF2 IS ALSO TERMINATING OVER A
 DOOR.
  
 5.HAZARDOUS EXHAUST SYSTEMS SHALL
 COMPLY WITH 2004 FMC 510.
  
 6.PLEASE PROVIDE ENERGY & SIZING
 CALCULATIONS IN ACCORDANCE WITH 2004 FBC
 CHAPTER 13, SECTION 13-400.0.ABC AND
 13-407.1ABC.1.
  
 7.PLEASE PROVIDE FLOOD ELEVATION
 CERTFICATE.PLEASE NOTE, THE CITY CODE
 REQUIRES AND ADDITIONAL 6" TO THE
 FEDERAL STANDARD.
  