2006-06-19 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. SUITABLE ROADS ARE TO PROVIDED DURING
 CONSTRUCTION FOR FIRE AND PARAMEDICAL
 EQUIPMENT.
  
 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING, AND AFTER CONSTRUCTION.
  
 4. PLEASE INDICATE HOW FIRE RESCUE
 ENTERS THROUGH THE ROLL GATE FENCE. WHAT
 SECURITY OR LOCKING ARRANGEMENTS WILL BE
 PRESENT AND IS A KNOX-BOX BEING
 PROPOSED.
  
 5. PRIVATE FIRE SERVICE MAINS AND
 HYDRANTS SHALL COMPLY WITH NFPA 24. THE
 STANDARD FOR PRIVATE FIRE SERVICE MAINS
 AND THEIR APPURTENANCES.
  
 6. NEW PRIVATE FIRE HYDRANTS TO COMPLY
 WITH UTILITY AND FIRE RESCUE STANDARDS.
  
 7. FIRE HYDRANT # 8 SHOULD BE RELOCATED
 IN FRONT OF GATE OR FENCE OPENING.
  
 8. ALL FIRE HYDRANTS SHALL BE PROVIDED
 WITH SEVEN AND HALF FEET CLEARANCE TO
 THE FRONT AND SIDES AND FOUR FEET TO THE
 REAR OF THEM. (PAGE C-21)
  
 9. ALL PAVEMENT ROAD SYSTEMS SHALL BE
 CAPABLE OF SUPPORTING 32 TONS FOR FIRE
 EQUIPMENT.
  
 10. ELECTRONIC SWITCHES, CHAIN AND LOCK
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICES.
  
 11. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEM.
  
 12. FIRE DEPARTMENT CONNECTIONS (FDC'S)
 SHALL BE LOCATED NO FARTHER THAN 150
 FEET FROM FIRE HYDRANTS.
  
 13. ALL FIRE DEPARTMENT CONNECTIONS
 (FDC'S) SHALL BE POSITIONED SO THEY
 CANNOT BE BLOCKED BY STORAGE, VESSELS,
 EQUIPMENT, ETC.
  
 14. BUILDING ADDRESSES REQUIRED ON
 PROPER ELEVATIONS. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS WITH 1" WIDTH SHALL BE
 PROVIDED.
  
 15. KNOX-BOXES WILL BE REQUIRED.
  
 16. NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTS SHOWN FOR COVERED WORK
 SHED VESSEL AREAS.
  
 17. PLEASE INDICATE ANY AND ALL
 HAZARDOUS MATERIALS PLANNED TO BE STORED
 AT THE NEW FACILITY. THESE MATERIALS
 INCLUDE FLAMMABLE AND COMBUSTIBLE
 LIQUIDS, CORROSIVES, OXIDIZERS,
 FLAMMABLE GASES, POSIONS, ETC.
  
 18. WHERE WILL FLAMMABLE LIQUIDS,
 SOLVENTS, ETC. PLANNED TO BE STORED.
  
 19. WHAT TYPE OF WORK IS PLANNED TO BE
 PERFORMED WHERE THE VESSELS ARE TO BE
 STORED.
  
 20. NO FIRE RATED DOORS SHOWN ON DOOR
 SCHEDULE. IS THERE NO FIRE RATING FOR
 BAYS 15 AND 16 LOCATED DIRECTLY IN FRONT
 OF THE VESSEL FIT UP AREA.
  
 21. WHERE IS THE FIBERGLASS AND GELCOAT
 MATERIALS PLANNED TO BE STORED OR
 UTILIZED.
  
 22. NEW FIRE ALARM SYSTEM SHALL MEET THE
 REQUIREMENTS OF BEING MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER