Plan Review Notes
Plan Review Notes For Permit 06030729
Permit Number 06030729
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-16 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE PANEL SCHEDULES AND LOAD
 CALCULATIONS FOR MSB5 AND PANELS A AND
 B'S THAT IT FEEDS, 215.5 NEC,
 106.3.5.1.2 FBC.
  
 2} INDICATE THE ELEVATION OF THE SERVICE
 EQUIPMENT AND TRANSFORMERS, IN RELATION
 TO THE ELECTRICAL DATUM PLANE. ARTICLE
 555.5.
  
 3}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT FOR MSB5 AND THE
 PANELS IT FEEDS.
  
 4} PROVIDE SPECIFICATIONS FOR ALL MAIN
 SERVICE EQUIPMENT.
  
 5} THE ELECTRIC ROOM IN BAY 1 THAT
 HOUSES MSB5 IS NOT IN COMPLIANCE WITH
 110.26(C)(2). THE PANIC HARDWARE
 REQUIRED IS NOT LISTED ON SHEET A-2.03
 FOR DOOR TYPE 1.12A.
  
 6} INDICATE MSB5 COMPLIANCE WITH 230.71
 THROUGH 230.79. THERE IS NO INDICATION
 OF A MAIN BREAKER ON THE PLAN.
  
 7} THE EMERGENCY WALL PACKS IN THE
 OFFICE LOBBY SHOULD BE ON CIRCUIT
 "A1-23" TO COMPLY WITH 700.12(E). ALSO
 THE LIGHTING SCHEDULE DOES NOT INDICATE
 THESE ARE BATTERY BACK-UP, PER SAME
 ARTICLE.
  
 8} PROVIDE SCHEDULES, RATINGS AND
 INDICATE COMPLIANCE WITH 230.71 THROUGH
 230.79 FOR MDP1 AND MDP2.
  
 9} THE CODE REFERENCES FOR NFPA 101 AND
 THE FLORIDA FIRE PREVENTION CODE ON
 SHEET GN-01 ARE INCORRECT. THEY ARE 2003
 FOR 101 AND 2004 FOR FFP. SEE FBC
 CHAPTER 35. PLEASE CORRECT ALL CODE
 REFERENCES WHERE THEY APPEAR ON PLANS.
  
 10} SEE ONE OF THE GN-01 SHEET ON ONE
 SET OF PLANS DOES NOT CONTAIN ALL
 INFORMATION THAT APPEARS ON THE OTHER
 TWO.
  
 11} INDICATE COMPLIANCE WITH CHAPTER 13,
 ENERGY CODE, ON THE PLANS, 413 THROUGH
 415.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  