| 2006-06-16 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PROVIDE PANEL SCHEDULES AND LOAD |
| | CALCULATIONS FOR MSB5 AND PANELS A AND |
| | B'S THAT IT FEEDS, 215.5 NEC, |
| | 106.3.5.1.2 FBC. |
| | |
| | 2} INDICATE THE ELEVATION OF THE SERVICE |
| | EQUIPMENT AND TRANSFORMERS, IN RELATION |
| | TO THE ELECTRICAL DATUM PLANE. ARTICLE |
| | 555.5. |
| | |
| | 3}PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT FOR MSB5 AND THE |
| | PANELS IT FEEDS. |
| | |
| | 4} PROVIDE SPECIFICATIONS FOR ALL MAIN |
| | SERVICE EQUIPMENT. |
| | |
| | 5} THE ELECTRIC ROOM IN BAY 1 THAT |
| | HOUSES MSB5 IS NOT IN COMPLIANCE WITH |
| | 110.26(C)(2). THE PANIC HARDWARE |
| | REQUIRED IS NOT LISTED ON SHEET A-2.03 |
| | FOR DOOR TYPE 1.12A. |
| | |
| | 6} INDICATE MSB5 COMPLIANCE WITH 230.71 |
| | THROUGH 230.79. THERE IS NO INDICATION |
| | OF A MAIN BREAKER ON THE PLAN. |
| | |
| | 7} THE EMERGENCY WALL PACKS IN THE |
| | OFFICE LOBBY SHOULD BE ON CIRCUIT |
| | "A1-23" TO COMPLY WITH 700.12(E). ALSO |
| | THE LIGHTING SCHEDULE DOES NOT INDICATE |
| | THESE ARE BATTERY BACK-UP, PER SAME |
| | ARTICLE. |
| | |
| | 8} PROVIDE SCHEDULES, RATINGS AND |
| | INDICATE COMPLIANCE WITH 230.71 THROUGH |
| | 230.79 FOR MDP1 AND MDP2. |
| | |
| | 9} THE CODE REFERENCES FOR NFPA 101 AND |
| | THE FLORIDA FIRE PREVENTION CODE ON |
| | SHEET GN-01 ARE INCORRECT. THEY ARE 2003 |
| | FOR 101 AND 2004 FOR FFP. SEE FBC |
| | CHAPTER 35. PLEASE CORRECT ALL CODE |
| | REFERENCES WHERE THEY APPEAR ON PLANS. |
| | |
| | 10} SEE ONE OF THE GN-01 SHEET ON ONE |
| | SET OF PLANS DOES NOT CONTAIN ALL |
| | INFORMATION THAT APPEARS ON THE OTHER |
| | TWO. |
| | |
| | 11} INDICATE COMPLIANCE WITH CHAPTER 13, |
| | ENERGY CODE, ON THE PLANS, 413 THROUGH |
| | 415. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |