| Notes |
| Date |
Text |
| 2006-03-31 00:00:00 | DENIED | | | | | | 1) EVALUATION REPORT 01506.11.05 FROM | | | EXTERIOR RESEARCH & DESIGN FOR THE | | | FLORIDA PRODUCT APPROVAL OF THE | | | GAF MODIFIED ROOFING SYSTEMS LISTS TWO | | | SYSTEMS FOR WOOD DECKS ON PAGE 2 OF | | | APPENDIX 1. NEITHER ONE LISTS THE SA | | | (SELF-ADHERING) LIBERTY CAP SHEET. THE | | | CAP SHEETS IN BOTH SYSTEMS LISTED FOR | | | WOOD DECKS ARE EITHER ASPHALT APPLIED OR | | | HEAT-WELDED. THIS PRODUCT APPROVAL IS | | | NOT FOR A SELF ADHERING CAP SHEET ON A | | | WOOD DECK. | | | | | | 2) ENGINEER DOES NOT SPECIFY THE | | | EVALUATION OR TEST REPORT THAT HE IS | | | BASING HIS ASSUMPTIONS ON. HIS DOCUMENT | | | MUST SPECIFY THE STANDARD AND METHOD | | | THAT HE IS USING TO DETERMINE ENHANCED | | | FASTENING. HIS REPORT DOES NOT APPEAR TO | | | RELATE TO THIS PRODUCT APPROVAL AS THE | | | SYSTEMS FOR WOOD DECKS ARE BONDED AND | | | ARE NOT MECHANICALLY FASTENED (SEE | | | APPENDIX 1). THE ENGINEER TO PROVIDE | | | COMPLETE ENGINEERING ANALYSIS AND | | | ROOFING STANDARDS USED TO PERFORM | | | CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|