Plan Review Notes
Plan Review Notes For Permit 06030641
Permit Number 06030641
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C)(1)- WALL COUNTER
 SPACES. A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTER SPACE
 THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS
 MORE THAN 600 MM (24 IN.) MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 2} 210.52(A) GENERAL PROVISIONS. IN
 EVERY KITCHEN, FAMILY ROOM, DINING ROOM,
 LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM, BEDROOM, RECREATION ROOM, OR
 SIMILAR ROOM OR AREA OF DWELLING UNITS,
 RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH
 (A)(3).
 (1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED
 HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT)
 FROM A RECEPTACLE OUTLET.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE WITH
 WIRE AND BREAKER SIZES PER 106.3.5.4
 FBC.
  
 4} THE COTTAGE MUST HAVE A DISCONNECT
 PER 225.31 GROUNDED PER 250.32, IF IT IS
 A SEPARATE STRUCTURE. PROVIDE A RISER
 DIAGRAM OF THE ENTIRE SERVICE SO
 COMPLIANCE WITH THESE ARTICLES CAN BE
 DETERMINED.
  
 PLEASE USE ACCEPTED ELCTRICAL SYMBOLS
 FOR THE DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  