 ******PROVISO******
 EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE
 TO BE BELOW CEILING. MANUAL SHUT OFF
 VALVE TO BE UPSTREAM. UNION TO BE DOWN
 STREAM OF MANUAL VALVE.
  
  
 IF WATER HEATER IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
  