Plan Review Notes
Plan Review Notes For Permit 06030638
Permit Number 06030638
Review Stop G
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00***DENIED***
 REFERENCE:FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. SUBMIT MANUFACTURE SHEETS FORGAS
 REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 410.2.
 REGULATORS NEED TO BE INDICATED ON
 DRAWING.
 2. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS NEEDS
 TO BE INDICATED ON DRAWING
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  
  
  