Plan Review Notes
Plan Review Notes For Permit 06030637
Permit Number 06030637
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-22 00:00:00 
  
 DENIED
  
 1) MARK WINDOW AND DOOR SIZES ON THE
 PLAN SKETCHES
  
 2) 2 DOOR NOA'S WERE PROVIDED, ARE 2
 DIFFERENT DOORS BEING USED? IF SO SHOW
 LOCATIONS OF EACH ON THE PLAN SKETCHES
  
 3) WHERE WINDOWS ARE TO BE JOINED
 TOGETHER IN A SERIES MULLIONS ARE USED
 BETWEEN THEM. PROVIDE MULLION PRODUCT
 APPROVALS
  
 4) PROVIDE STATE OF FLORIDA PRODUCT
 APPROVAL PAGES WHEN AVAILABLE. FL#
 889-R2 FOR HARDIEBOARD AND FL# 6738 FOR
 TRACO WINDOWS, ALSO NOA HAS BEEN REVISED
 FOR TRACO WINDOWS NEW NOA IS 05-0930.03
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716