| Plan Review Notes For Permit 06030614 |
| Permit Number |
06030614 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-14 00:00:00 | DENIED | | | REFERENCE: FBC-2004 CHAPTER 1 | | | | | | 1. SINCE THIS IS THE DISCHARGE IS FROM | | | THE POOL EQUIPMENT, THE POOL ENGINEER | | | SHALL SIGN, SEAL, DATE ALL COPIES. TITLE | | | BLOCKS WITH ALL REQUIRED INFORMATION IS | | | REQUIRED ON EACH SHEET. SECTION 106.1 | | | | | | 2. SUBMIT A DETAIL FOR THE PAD THAT THE | | | TANK WILL BE SET UPON. INDICATE THE | | | THICKNESS OF THE SLAB AND INDICATE ANY | | | REINFORCEMENT REQUIRED. THE TOTAL WEIGHT | | | OF THE WATER IN THE TANK WILL BE 9,960 | | | LBS FOR 1,200 GALS. TO 14,161 LBS OF | | | WATER FOR 1,700 GALS. PLUS THE WEIGHT OF | | | THE STORAGE TANK. PLEASE PROVIDE | | | CALCULATIONS INDICATING TOTAL WEIGHT. | | | SUBMIT A DETAIL FOR THECONNECTIONS TO | | | THE PAD SHOWING COMPLIANCE WITH THE | | | REQUIREMENT TO MEET THE 140 MPH | | | WINDLOAD. SECTION 106.1.1. | | | | | | 3. PLANS SHALL BE ROUTED TO THE CITY | | | ENGINEERING DEPT FOR APPROVAL PRIOR TO | | | RESUBMITTING TO CONSTRUCTION SERVICES | | | FOR APPROVAL AS A REVISION. (SEE | | | ATTACHED LETTER). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|