Date Text
2006-09-14 00:00:00DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SINCE THIS IS THE DISCHARGE IS FROM
 THE POOL EQUIPMENT, THE POOL ENGINEER
 SHALL SIGN, SEAL, DATE ALL COPIES. TITLE
 BLOCKS WITH ALL REQUIRED INFORMATION IS
 REQUIRED ON EACH SHEET. SECTION 106.1
  
 2. SUBMIT A DETAIL FOR THE PAD THAT THE
 TANK WILL BE SET UPON. INDICATE THE
 THICKNESS OF THE SLAB AND INDICATE ANY
 REINFORCEMENT REQUIRED. THE TOTAL WEIGHT
 OF THE WATER IN THE TANK WILL BE 9,960
 LBS FOR 1,200 GALS. TO 14,161 LBS OF
 WATER FOR 1,700 GALS. PLUS THE WEIGHT OF
 THE STORAGE TANK. PLEASE PROVIDE
 CALCULATIONS INDICATING TOTAL WEIGHT.
 SUBMIT A DETAIL FOR THECONNECTIONS TO
 THE PAD SHOWING COMPLIANCE WITH THE
 REQUIREMENT TO MEET THE 140 MPH
 WINDLOAD. SECTION 106.1.1.
  
 3. PLANS SHALL BE ROUTED TO THE CITY
 ENGINEERING DEPT FOR APPROVAL PRIOR TO
 RESUBMITTING TO CONSTRUCTION SERVICES
 FOR APPROVAL AS A REVISION. (SEE
 ATTACHED LETTER).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]