Plan Review Notes
Plan Review Notes For Permit 06030614
Permit Number 06030614
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-10 00:00:00PROVISO
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 3) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR. AT
 THE PULL SIDE OF DOORS A 18"MIN IS
 REQUIRED. SEE THE TWO SINGLE DOORS
 LEADING TO THE POOL. SHEETS S-1 AND S-2
 SHOW THE DOORS SWINGING IN WHILE SHEET
 S-5 SHOWS THE SAME DOORS SINGING OUT
 PLEASE CLARIFY.
  
  
  