Plan Review Notes
Plan Review Notes For Permit 06030606
Permit Number 06030606
Review Stop E
Sequence Number 3
Notes
Date Text
2006-07-23 00:00:00UNSAT 3RD REVIEW
  
  
 1) NOTE:PLAN STILL SHOWS NO CONTROL OF
 LIGHTING PER 13-415 OF THE FBC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3
 PLEASE SEE 13-415.1.AB.1,13-415.2.ABC.1
 AND TABLES 415.2.C.1, 415.2.B.1
 PLEASE KNOW ORIGIANL DESIGN WAS UNDER
 THE 2001 FBC , HOWEVER PLEASE SEE
 DESIGNS ARE UNDER 2004 FBC AS THESE WERE
 SUBMITTED FOR PERMIT AFTER OCT. 1ST 2005
 WHEN THE NEW CODE WENT INTO EFFECT.
 PLEASE ALSO SEE 13-415.1AB
  
 2) NOTE: PLEASE SEE PLANS, 1999 NEC IS
 REFERENCED ON COVER FBC
 USES 2002 NEC, CHAPTER 27.
  
 3) NOTE: PLEASE SEE AS THE SAME REVIEW
 COMMENTS HAVE NOT BEEN ADDRESSEDA 4X
 FEE HAS NOW BEEN ASSESSED FOR THE PLAN
 REVIEW PORTION OF THE BASE PERMIT FEE.
 PLEASE SEE 553.802B.
 PLEASE KNOW, THIS IS A REQUIRED FEE
 UNDER FLORIDA STATUES AND WILL APPLY FOR
 EACH REVIEW IF THE SAME CODE COMPLIANCE
 COMMENT(S) ARE NOT ADDRESSED.
 PLEASE KNOW AS FEE OF $1680.00 MUST BE
 PAID BEFORE RESUBMITTING PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 JAKE LEAHY
 561-805-6740
 OR
 DEWEY PALMER
 561-805-6717