| Plan Review Notes For Permit 06030606 |
| Permit Number |
06030606 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-19 00:00:00 | | | | 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1, | | | 2004 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE. SEE SHEET T.1 | | | | | | 2) THE UL ASSEMBLY X526 ON THE DRAWINGS | | | DOES NOT MATCH THE DESIGN IN THE UL | | | BOOK. SUBMIT A DESIGN WHICH CORRESPOND | | | WITH ONE OF THE DESIGNS IN THE UL BOOK. | | | SEE SHEET A.1. | | | | | | 3) PRODUCT APPROVALS ARE REQUIED FOR THE | | | NEW STOREFRONT AND DOORS. | | | WPB ADMIN CODE 106.3* PRODUCT APPROVALS. | | | THOSE PRODUCT WHICH ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | |
|