2006-06-19 00:00:00 
 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE. SEE SHEET T.1
  
 2) THE UL ASSEMBLY X526 ON THE DRAWINGS
 DOES NOT MATCH THE DESIGN IN THE UL
 BOOK. SUBMIT A DESIGN WHICH CORRESPOND
 WITH ONE OF THE DESIGNS IN THE UL BOOK.
 SEE SHEET A.1.
  
 3) PRODUCT APPROVALS ARE REQUIED FOR THE
 NEW STOREFRONT AND DOORS.
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  