| 2006-07-16 00:00:00 | IN ELEC FOR REVIEW, FROM ZONING ON 7/11 |
| | **** UNSAT **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE SOME NEW NOTES. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW AS NOTED, |
| | WITH NEW NOTES ADDED TO THE BOTTOM OF |
| | THE FIRST REVIEW NOTES. |
| | |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK/NO. ADDRESSED COMMENT, |
| | HOWEVER DUE TO CHANGES MADE BY COMMENT, |
| | PLEASE SEE THE MISPRINT WAS REVISE, |
| | HOWEVER PLEASE KNOW, THE CONDUIT |
| | EXTENDING FROM GRND TO METER SHALL BE |
| | SCHEDULE 80 AS THIS IS AREA IS |
| | CONSIDERED SUBMIT TO PHYSICAL DAMAGE. |
| | 352.10F |
| | |
| | ** PREVIOUS REVIEW NOTE**PLEASE SEE |
| | UNDERGROUND CONDUITS |
| | WHICH MENTIONS THE USE OF SCHEDULE "90" |
| | PVC?? PLEASE VERIFY AS THIS IS NOT A |
| | COMMON ITEM, NOR IS IT LISTED IN THE |
| | NEC. |
| | 215.5 |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: NO, PLEASE SEE THIS STILL DOES |
| | NOT SEEM TO BE COMPLETE AT THIS TIME FOR |
| | INTENDED LOADS, DISCONNECTING MEANS ECT. |
| | PLEASE ALSO SEE THAT MANUFACTURES |
| | SPECS/CUT SHEETS WERE NOT SUBMITTED. |
| | PLEASE KNOW, IT IS NOTED THAT THE |
| | RESPONSE MENTIONS THIS WOULD BE DONE AT |
| | A LATER DATE , HOWEVER THIS IS REQUIRED |
| | AT THIS TIME IF SYSTEM IS GOING TO BE |
| | UNDER MAIN HOUSE PERMIT. PLEASE SEE |
| | PLANS ARE NOT DETAILED ENOUGH FOR |
| | TRANSFER OF POWER AND WHERE THAT IS |
| | TAKING PLACE, DISCONNECTING MEANS ETC. |
| | ** PLEASE KNOW, THE PV SYSTEM MAY |
| | EXCLUDED AND SUBMITTED UNDER A SEPARATE |
| | PERMIT AT A LATER DATE. NO ELECTRICAL |
| | FOR ANY DEVICES SHOWN ON PLANS WOULD BE |
| | PERMITTED AT THIS TIME. |
| | ** PLEASE KNOW, EQUIPMENT MAY ALWAYS BE |
| | REVISED. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE COMPLETE PLANS FOR |
| | PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL |
| | MANUFACTURES SPECS/ CUT SHEETS FOR |
| | EQUIPMENT TO BE INSTALLED. |
| | PLEASE BE SURE ALL SHEETS INDICATE A |
| | LISTING FROM A NRTL. |
| | PLEASE BE SURE TO SEE 690 OF THE NEC. |
| | ** PLEASE BE SURE TO ALSO SEE BLDG |
| | COMMENTS WITH RESPECT TO WIND LOAD |
| | CALCULATIONS REQUIRED FOR NEW EQUIPMENT |
| | BEING INSTALLED ON ROOF. |
| | |
| | 9) NOTE: NO, PLEASE SEE THIS IS THE SAME |
| | AS ABOVE. PLEASE SUBMIT AT THIS TIME OR |
| | KNOW, THE LIGHTING CONTROL SYSTEM CAN BE |
| | DONE UNDER A SEPARATE PERMIT. NO WIRING |
| | MAY BE INSTALLED UNTIL THAT PERMIT IS |
| | ISSUED. |
| | ** ONCE AGAIN, EQUIPMENT CAN ALWAYS BE |
| | REVISED. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SUBMIT COMPLETE SPECS/CUT |
| | SHEETS FOR NEW LIGHTING CONTROL SYSTEM. |
| | PLEASE BE SURE ALL SHEETS INDICATE A |
| | LISTING FROM A NRTL. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK, HOWEVER SEE NOTES |
| | REGARDING LOAD CALCUALTIONS. |
| | |
| | 13) NOTE:NO, PLEASE SEE LAUNDRY |
| | CIRCUIT IS SHOWN AT .40VA. |
| | WASHER REVISED. |
| | |
| | ** PREVIOUS PLEASE SEE 220.16, 210.11C2 |
| | FOR MINIMUM VA FOR LAUNDRY AND WASHER. |
| | |
| | 14) NOTE:OK. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: NO, PLEASE SEE THESE WERE |
| | ADDED, HOWEVER PLEASE SEE REDLINED |
| | PLANS, AS GFI RECEPT IS REQUIRED TO BE |
| | WITHIN 2' OF THE END/START OF THE |
| | COUNTERSPACE. ** THIS CAN BE REDLINED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE 210.52C1 FOR KITCHEN |
| | COUNTER SPACE RECEPTACLES MISSING. |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE: OK. |
| | |
| | 20) NOTE:NO, PLEASE SEE CALCUALITONS |
| | WERE SUBMITTED ON PLANS AND IN SPEC |
| | BOOKS, HOWEVER THEY ARE REFERENCING |
| | CODES NOT IN THE CURRENT 2002 NEC. |
| | PLEASE ALSO SEE 220, 220.11 ETC FOR WHAT |
| | LOADS ARE PERMITTED TO BE DERATED UNDER |
| | THE TABLE. PLEASE KNOW, NOT ALL LOADS AS |
| | SHOWN IN LOAD CALCS MAY BE DERATED UNDER |
| | THE SAME 220.11 |
| | PLEASE KNOW, LOADS MAY BE DONE UNDER |
| | 220.31 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING MINIMUM |
| | LOAD CALCULATIONS PER NEC.220 |
| | |
| | 21) NOTE: OK. |
| | |
| | 22) NOTE: NO, RESPONSE MENTIONS THIS IS |
| | THE LEGAL SIGNATURE, HOWEVER COULD NOT |
| | LOCATE THE LETTER FROM THE ENGINEER OF |
| | RECORD. THE LTR WILL BE PLACED IN FILE |
| | AS PREVIOUSLY NOTED. |
| | |
| | ** PREVIUOS REVIEW NOTE ** |
| | PLEASE SEE FS 471.025 WHICH |
| | REQUIRES THE LEGAL SIGNATURE FOR THE |
| | ENGINEER OF RECORD. PLANS APPEAR TO |
| | CONTAIN INITIALS, IF INDEED THIS IS THE |
| | LEGAL SIGNATURE, PLEASE PROVIDE A |
| | SIGNED, DATED, SEALED LETTER TO ATTEST |
| | TO THE LEGAL SIGNATURE. THIS LETTER IS |
| | REQUIRED TO BE CORRECTLY NOTARIZED UNDER |
| | FS 117.05 |
| | PLEASE KNOW, THIS WILL GO INTO OUR |
| | SIGNATURE FILE FOR ANY FUTURE REFERENCED |
| | NEEDED FOR SIGNATURE. |
| | |
| | ** NEW NOTES *** |
| | |
| | 23) NOTE: PLEASE CLARIFY THE SYMBOL ON |
| | PLANS AS "SF" AT DOOR LOCATIONS ETC , AS |
| | THIS DEVICE IS NOT ON SYMBOL LEGEND. |
| | |
| | 24) NOTE: PLEASE SEE SOME SORT OF |
| | LIGHTING FIXTURE IS BEING SHOWN IN |
| | CLOSET WHICH DOES NOT SEEM MIN |
| | CLEARENCES PER 410.8. PLEASE ALSO SEE |
| | OTHER TYPE OF FLOURESCENT DOWN LTS, |
| | WHICH SEEM TO BE DIRECLTY OVER SHELVING |
| | AREA IN ONE CLOSET. |
| | PLEASE SUBMIT SPEC/MANUFACTURE CUT |
| | SHEETS FOR LIGHTING BEING PROPOSED AS |
| | "STRIP LIGHTING" OF SOME KIND. |
| | PLEASE SEE 410.8 |
| | |
| | 25) NOTE: PLEASE SEE THE WATER HEATER IS |
| | BEING SHOWN AS 4.5KW, HOWEVER THE OCP IS |
| | SHOWN AS 50A'S? |
| | PLEASE SEE MIN OCP FOR THIS IS 125%, |
| | HOWEVER MAX OCP IS 150%.(30A) PLEASE |
| | ALSO SEE CONDUCTOR SIZE SHOWN AT #6 |
| | NEEDS ADJUSTING AS #6 IS NOT RATED UNDER |
| | THE LUGS OF A 30A BRKR. |
| | 422.11E3 |
| | |
| | ** PLEASW KNOW, THE DETAILED RESPONSE |
| | WAS APPRECIATED AS THIS HELPS IN THE |
| | REVIEW PROCESS. |
| | |
| | |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW, IF THIS PERMIT IS GOING |
| | TO INLCUDE LIGHTING CONTROL SYSTEM AND |
| | PHOTOVOLTAIC SYSTEM, VALUE FOR COMPLETE |
| | SCOPE OF WORK WILL BE REQUIRED TO BE |
| | INCREASED, AS THE VALUES BASED IN THE |
| | TABLES FOR THE FBC DOES NOT INLCUDE |
| | THESE SPECIALIZED ELECTRICAL SYSTEMS. |
| | PLEASE PROVIDE COMPLETE CONTRACT FOR ALL |
| | TRADES FOR SCOPE OF WORK OR ADJUST VALUE |
| | IF THESE WILL BE PERMITTED UNDER HOUSE |
| | PERMIT. |
| | PLEASE ALOS KNOW, THE ELECTRICAL |
| | CONTRACTOR UNDER HOUSE PERMIT WILL ALSO |
| | BE RESPONSIBLE FOR ALL WORK EVEN IF DONE |
| | BY A SUB CONTRACTOR. |
| | FBC 108.3 |
| | ** PLEASE HAVE CONTRACTOR CALL TO GO |
| | OVER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |