| Plan Review Notes For Permit 06030523 |
| Permit Number |
06030523 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-21 00:00:00 | DENIED; | | | 1.SHOW SIZE OF ROOF AREA TO DRAIN TO | | | STORAGE TANK, AND SIZE ALL HORIZONTAL | | | PIPING. SEE FBC-2004 PLUMBING TABLE | | | 1106.3.ALSO SHOW SIZE OF ROOF GUTTERS | | | AND DOWN SPOUTS. | | | 2.A/C CONDENSATE IS NOT PERMITED TO GO | | | TO SANITARY SEWER. UTILITY ORD. INSTALL | | | A DRY WELL FOR CONDENSATE. | | | 3.SANITARY RISER DIAGRAM IS REQUIRED SEE | | | WPB AMENDMENTS TO THE FBC CHAPTER 1, | | | SEC106.3.5.4(9) | | | 4. HORIZONTAL DRY VENTS ARE NOT PERMITED | | | IN THE SANITARY DRAINAGE SYSTEM. SEE | | | GARAGE FLOOR DRAINS, BIDET, ETC. SEC. | | | 905.3. | | | 5.FLOOR DRAINS IN GARAGE AREA MAY | | | REQUIRE A SAND AND OIL SEPARATOR. MORE | | | DETAIL REQUIRED WHY ARE TWO FLOOR DRAINS | | | NEEDED IN GARAGE? | | | 6.SEE TABLE 704.1 FOR THE MINIMUM SLOPE | | | OF HORIZONTAL DRAINAGE PIPE. | | | 7.PLEASE SHOW A DETAIL OF WATER HEATER | | | ASSEMBY. NOT ENOUGH DETAILS. COULD NOT | | | FIND MEP SPECIFCATIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|