| | ******* UNSAT ******** |
| | |
| | 1) NOTE: PLEASE ADD NOTE WHICH STATES |
| | THAT THE LIGHTNING PROTECTION SYSTEM |
| | SHALL BE UNDER A SEPARATE PERMIT. |
| | |
| | 2) NOTE: PLEASE CLARIFY PANEL 1B AND 1C, |
| | AS THESE ARE SHOWN WITH ?FEED-THRU? |
| | LUGS? ARE THERE OTHER PANELS? |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEE 250.6, 250.24B, |
| | RISER DIAGRAM SHOWS "EQUIPMENT GROUNDING |
| | CONDUCTORS" FROM FPL TO THE FIRST MEANS |
| | OF DISCONNECT. PLEASE KNOW, THE |
| | "EQUIPMENT GRND" SHOULD ONLY BE |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 4) NOTE: PLEASE CLARIFY USE OF WHAT |
| | APPEARS TO BE A "CT" FOR METERING. THIS |
| | IS UNCLEAR AS THE PLANS INDICATE A |
| | METER, BUT THE PLANS DO NOT SHOW A METER |
| | ON HOUSE? |
| | IF A CT IS NOT USED, PLEASE INCLUDE |
| | METER CAN ON RISER AND ADJUST CONDUCTORS |
| | ETC. |
| | PLEASE OBTAIN A LETTER FROM AN FPL |
| | SERVICE PLANNER, WHICH STATES THAT A |
| | "CT" IS GOING TO BE USED. |
| | |
| | 5) NOTE: PLEASE SEE UNDERGROUND CONDUITS |
| | WHICH MENTIONS THE USE OF SCHEDULE "90" |
| | PVC?? PLEASE VERIFY AS THIS IS NOT A |
| | COMMON ITEM, NOR IS IT LISTED IN THE |
| | NEC. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE VERIFY THE MIN DEPTH OF |
| | UNDER GROUND SERVICE ENTRANCE CONDUITS. |
| | PLEASE SEE THE MIN DEPTH PER FPL GUIDE |
| | LINES IS 24INCHES TO THE TOP OF THE |
| | CONDUITS. |
| | PLEASE ALSO SEE NOTE/DETAIL MENTIONS |
| | 18INCHES UNDER ROADS? PLEASE SEE 300.5 |
| | FOR MIN |
| | DEPTHS. |
| | |
| | 7) NOTE: PLEASE SEE MINIMUM GROUNDING |
| | ELECTRODE SYSTEM TO BE SHOWN PER |
| | 250.50,250.52 |
| | PLEASE INCLUDE, CWP, FOOTER STEEL, AT A |
| | MIN. |
| | |
| | 8) NOTE: PLEASE COMPLETE PLANS FOR |
| | PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL |
| | MANUFACTURES SPECS/ CUT SHEETS FOR |
| | EQUIPMENT TO BE INSTALLED. |
| | PLEASE BE SURE ALL SHEETS INDICATE A |
| | LISTING FROM A NRTL. |
| | PLEASE BE SURE TO SEE 690 OF THE NEC. |
| | ** PLEASE BE SURE TO ALSO SEE BLDG |
| | COMMENTS WITH RESPECT TO WIND LOAD |
| | CALCULATIONS REQUIRED FOR NEW EQUIPMENT |
| | BEING INSTALLED ON ROOF. |
| | |
| | 9) NOTE: PLEASE SUBMIT COMPLETE |
| | SPECS/CUT SHEETS FOR NEW LIGHTING |
| | CONTROL SYSTEM. PLEASE BE SURE ALL |
| | SHEETS INDICATE A LISTING FROM A NRTL. |
| | |
| | 10) NOTE: PLEASE SEE 2002 NEC 210.12B |
| | FOR MIN ARC FAULT PROTECTION REQUIRED |
| | FOR ALL OUTLETS IN SLEEPING ROOMS. |
| | PLEASE SEE THIS INCLUDES, LIGHTS, |
| | RECEPTS, SD'S, FANS ETC. PLEASE VERIFY |
| | THE PROTECTION AND HOW THESE WILL BE |
| | TIED INTO LIGHTING CONTROL SYSTEMS. |
| | |
| | 11) NOTE: PLEASE SEE NFPA-72 11.5.1.1 |
| | WHICH REQUIRES A SD ON EACH LEVEL OF A |
| | MULTI-LEVEL BUILDING IN THE IMMEDIATE |
| | VICINITY OF STAIRS LEADING TO THE FLOOR |
| | ABOVE. |
| | |
| | 12) NOTE: PLEASE MININUM VA REQUIRED |
| | FOR SMALL APPL CIRCUITS PER 220.12, |
| | 210.52B1,210.11C1 |
| | |
| | 13) NOTE: PLEASE SEE 220.12, 210.11C2 |
| | FOR MINIMUM VA FOR LAUNDRY AND WASHER. |
| | |
| | 14) NOTE: PLEASE SEE 220.18 FOR MINIMUM |
| | VA FOR DRYER LOADS. |
| | |
| | 15) NOTE: PLEASE SEE 210.8A7 FOR ALL |
| | RECEPTS LOCATED WITHIN 6 FT OF A SINK TO |
| | BE GFI/ GFI PROTECTED. |
| | UPPER LAUNDRY ROOM. |
| | |
| | 16) NOTE: PLEASE SEE KEY NOTE P2 WHICH |
| | STATES ALL OUTSIDE GFI RECEPTS TO BE |
| | HALF SWITCHED. PLEASE KNOW, THIS IS NOT |
| | POSSIBLE AS GFI RECEPTS ARE NOT MADE TO |
| | BE HALF SWITCH. THERE ARE ONLY LINE OR |
| | LOAD CONNECTIONS. |
| | PLEASE SEE 210.52E FOR MINIMUM REQUIRED. |
| | |
| | 17) NOTE: PLEASE 210.52C1 FOR KITCHEN |
| | COUNTER SPACE RECEPTACLES MISSING. |
| | |
| | 18) NOTE: PLEASE SEE MISSING CIRCUITING |
| | FOR SD'S. |
| | 215.5 |
| | |
| | 19) NOTE: PLEASE SEE PANEL "A" IS |
| | MISSING LOADS FOR PANEL "C". |
| | 215.5 |
| | |
| | 20) NOTE: PLEASE SEE MISSING MINIMUM |
| | LOAD CALCULATIONS PER NEC.220 |
| | |
| | 21) NOTE: PLEASE MAKE REFERENCE TO THE |
| | FOLLOWING CURRENT CODES IN EFFECT. 2002 |
| | NFPA-70, 2002 NFPA-72 |
| | |
| | 22) NOTE: PLEASE SEE FS 471.025 WHICH |
| | REQUIRES THE LEGAL SIGNATURE FOR THE |
| | ENGINEER OF RECORD. PLANS APPEAR TO |
| | CONTAIN INITIALS, IF INDEED THIS IS THE |
| | LEGAL SIGNATURE, PLEASE PROVIDE A |
| | SIGNED, DATED, SEALED LETTER TO ATTEST |
| | TO THE LEGAL SIGNATURE. THIS LETTER IS |
| | REQUIRED TO BE CORRECTLY NOTARIZED UNDER |
| | FS 117.05 |
| | PLEASE KNOW, THIS WILL GO INTO OUR |
| | SIGNATURE FILE FOR ANY FUTURE REFERENCED |
| | NEEDED FOR SIGNATURE. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |