Plan Review Notes For Permit 06030503
Permit Number 06030503
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-13 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL PLAN ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 2) MACHANICAL PLANS MUST ALSO HAVE ON
 THEM THE A/C EQUIPMENT LISTING WITH ALL
 THE PERTINENT INFORMATION, AND SHOW ALL
 DUCT (FLEX) SIZES.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 4) PLEASE PROVIDE WITH TWO COPYS OF THE
 ENERGY CALCULATIONS A MANUAL J (LONG
 FORM) SHOWING CFM'S. TO EACH ROOM, PER
 2004 FBC 13-607.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.