| 2006-10-12 15:08:54 | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWINGS CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE RISER DIAGRAM MARKED " T TYPICAL " NEEDS TO BE |
| | SPECIFIC. THERE IS TWO METERS SHOWN AND TWO 150 AMP |
| | PANELS MARKED "A" AND "B". WHERE IS THE RISER FOR "C" |
| | AND "D"? WHAT ARE THE DISCONNECTS SHOWN TO THE SIDE OF |
| | THE METERS? |
| | |
| | 2} THE LOAD CALCULATIONS DO NOT CORRELATE WITH THE |
| | EQUIPMENT IN THE PANEL SCHEDULE. SEE ARTICLE 220 IN THE |
| | 2002 NEC. USE SECTIONS I AND II OR 220.30, 31, OR 32. |
| | INDICATE WHICH TABLE OR ARTICLE IS USED ON THE PLAN. |
| | |
| | 3}PANEL MDP IS ON THE PLAN WITH A SCHEDULE, BUT NOT |
| | ON THE RISER. |
| | |
| | 4} THE GROUNDING ELECTRODE CONDUCTOR IS INCORRECT FOR |
| | THE SERVICE THAT IS SHOWN, SEE 250.66 AND SIZE |
| | ACCORDINGLY. |
| | |
| | 5} } PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 6} THE PLAN SHOWS "SERVICE PANELS " OUTSIDE, AND |
| | INSIDE. CORRELATE SAME ON RISER. |
| | |
| | THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED |
| | "GROUND FLOOR PLAN" SHEET E-1. |
| | |
| | 7} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), PUT IN THE SCHEDULE. |
| | |
| | 9} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER |
| | ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS |
| | WELL AS VOLTAGES. |
| | |
| | 10} TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER |
| | 210.11(C)(1) MUST APPEAR ON CALCS AND SCHEDULES. |
| | |
| | 11} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 12} THE BEDROOMS,AND OFFICE MUST COMPLY WITH THE |
| | REQUIRED RECEPTACLE SPACING PER 210.52(A). |
| | |
| | 13} THE DETECTOR IN THE KITCHEN MUST BE HEAT AND NOT |
| | SMOKE PER NFPA-72. |
| | |
| | THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED |
| | "FIRST FLOOR PLAN" SHEET E-1. |
| | |
| | 14} INDICATE THE DIFFERENCE BETWEEN "GROUND " AND |
| | "FIRST" FLOOR. |
| | |
| | 15} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 16} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), PUT IN THE SCHEDULE. |
| | |
| | 17} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER |
| | ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS |
| | WELL AS VOLTAGES. |
| | |
| | 18} TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER |
| | 210.11(C)(1) MUST APPEAR ON CALCS AND SCHEDULES. |
| | |
| | 19}KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 20} INDICATE COMPLIANCE WITH 210.12, ARC FAULT |
| | PROTECTION. |
| | |
| | 21} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER |
| | ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS |
| | WELL AS VOLTAGES. |
| | |
| | 22}PENINSULAR COUNTER SPACES. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH PENINSULAR COUNTER |
| | SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR |
| | GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| | GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE |
| | CONNECTING EDGE. 210.52(C)(3). |
| | |
| | THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED |
| | "708-1/2 (A)" SHEET E-1. |
| | |
| | 23} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 24} PROVIDE A PANEL SCHEDULE AND RISER DIAGRAM. |
| | |
| | 26} THE BEDROOMS,AND LOUNGE MUST COMPLY WITH THE |
| | REQUIRED RECEPTACLE SPACING PER 210.52(A) |
| | |
| | 27} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 28} 210.52( E) OUTDOOR OUTLETS. FOR A ONE-FAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2 |
| | FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND |
| | BACK OF THE DWELLING. SEE 210.8(A)(3). |
| | |
| | THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED |
| | "708-1/2 (B)" SHEET E-1. |
| | |
| | 29} THE BEDROOM AND LOUNGE MUST COMPLY WITH THE |
| | REQUIRED RECEPTACLE SPACING PER 210.52(A) |
| | |
| | 30} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 31}KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | ONE SET OF PLANS IS BEING RETAINED TO BE SENT TO THE |
| | STATE BOARD OF ARCHITECTURE FOR VIOLATIONS OF 481.223 |
| | FLORIDA STATUTES. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |