Plan Review Notes
Plan Review Notes For Permit 06030498
Permit Number 06030498
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-12 15:08:54NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWINGS CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM MARKED " T TYPICAL " NEEDS TO BE
 SPECIFIC. THERE IS TWO METERS SHOWN AND TWO 150 AMP
 PANELS MARKED "A" AND "B". WHERE IS THE RISER FOR "C"
 AND "D"? WHAT ARE THE DISCONNECTS SHOWN TO THE SIDE OF
 THE METERS?
  
 2} THE LOAD CALCULATIONS DO NOT CORRELATE WITH THE
 EQUIPMENT IN THE PANEL SCHEDULE. SEE ARTICLE 220 IN THE
 2002 NEC. USE SECTIONS I AND II OR 220.30, 31, OR 32.
 INDICATE WHICH TABLE OR ARTICLE IS USED ON THE PLAN.
  
 3}PANEL MDP IS ON THE PLAN WITH A SCHEDULE, BUT NOT
 ON THE RISER.
  
 4} THE GROUNDING ELECTRODE CONDUCTOR IS INCORRECT FOR
 THE SERVICE THAT IS SHOWN, SEE 250.66 AND SIZE
 ACCORDINGLY.
  
 5} } PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 6} THE PLAN SHOWS "SERVICE PANELS " OUTSIDE, AND
 INSIDE. CORRELATE SAME ON RISER.
  
 THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED
 "GROUND FLOOR PLAN" SHEET E-1.
  
 7} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), PUT IN THE SCHEDULE.
  
 9} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER
 ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS
 WELL AS VOLTAGES.
  
 10} TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER
 210.11(C)(1) MUST APPEAR ON CALCS AND SCHEDULES.
  
 11} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 12} THE BEDROOMS,AND OFFICE MUST COMPLY WITH THE
 REQUIRED RECEPTACLE SPACING PER 210.52(A).
  
 13} THE DETECTOR IN THE KITCHEN MUST BE HEAT AND NOT
 SMOKE PER NFPA-72.
  
 THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED
 "FIRST FLOOR PLAN" SHEET E-1.
  
 14} INDICATE THE DIFFERENCE BETWEEN "GROUND " AND
 "FIRST" FLOOR.
  
 15} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 16} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), PUT IN THE SCHEDULE.
  
 17} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER
 ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS
 WELL AS VOLTAGES.
  
 18} TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER
 210.11(C)(1) MUST APPEAR ON CALCS AND SCHEDULES.
  
 19}KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 20} INDICATE COMPLIANCE WITH 210.12, ARC FAULT
 PROTECTION.
  
 21} THE WATER HEATER, CONDENSER, RANGE AND AIR HANDLER
 ARE SHOWN ON SINGLE POLE BREAKERS. VERIFY THE LOAD AS
 WELL AS VOLTAGES.
  
 22}PENINSULAR COUNTER SPACES. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH PENINSULAR COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE
 CONNECTING EDGE. 210.52(C)(3).
  
 THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED
 "708-1/2 (A)" SHEET E-1.
  
 23} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 24} PROVIDE A PANEL SCHEDULE AND RISER DIAGRAM.
  
 26} THE BEDROOMS,AND LOUNGE MUST COMPLY WITH THE
 REQUIRED RECEPTACLE SPACING PER 210.52(A)
  
 27} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 28} 210.52( E) OUTDOOR OUTLETS. FOR A ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2
 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING. SEE 210.8(A)(3).
  
 THE FOLLOWING COMMENTS REFERENCE THE DRAWING MARKED
 "708-1/2 (B)" SHEET E-1.
  
 29} THE BEDROOM AND LOUNGE MUST COMPLY WITH THE
 REQUIRED RECEPTACLE SPACING PER 210.52(A)
  
 30} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 31}KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 ONE SET OF PLANS IS BEING RETAINED TO BE SENT TO THE
 STATE BOARD OF ARCHITECTURE FOR VIOLATIONS OF 481.223
 FLORIDA STATUTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676