| Date |
Text |
| 2006-08-14 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. PER THE NOTE ON SHEET M-1 THAT |
| | INDICATES ALL EXISTING CAST IRON PIPES |
| | TO BE REPLACED BY CODE APPROVED PVC |
| | PIPE, THE FOLLOWING IS REQUIRED FOR THE |
| | 2 STORY APARTMENT BUILDING. |
| | (A) PER FBC-2004 PLUMBING, SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS. |
| | 2. NOTE: THE BATHTUB INDICATED ON SHEET |
| | M-1, 708-1/2 A, IS NOT VENTED PER |
| | FBC-2004 PLUMBING, SECTION #901.2.1. |
| | PLEASE REFERENCE THE CORRECTED DRAWING |
| | ON SHEET M-1 IN RED INK FOR RESUBMITTAL. |
| | 3. NOTE: THE SANITARY ISOMETRIC RISER |
| | DIAGRAMS INDICATED ON SHEET M-1 DO NOT |
| | REFLECT THE FLOOR PLAN, PLEASE REFERENCE |
| | THE CORRECTED DRAWINGS ON SHEET M-1 IN |
| | RED INK FOR RESUBMITTAL. |
| | 4. NOTE: PER FBC-2004 PLUMBING, SEC |
| | 406.3 THE FOLLOWING NEEDS TO BE |
| | CORRECTED ON THE WASHING MACHINE |
| | INDICATED ON SHEET M-1, 708-1/2 A AND B |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. PLEASE REFERENCE THE CORRECTED |
| | DRAWING ON SHEET M-1 FOR RESUBMITTAL. |
| | 5. PER THE FLORIDA ADMINISTRATIVE CODE |
| | ITEMS #2 AND #6 ARE STILL NOT INDICATED |
| | ON THE TITLE BLOCK PLEASE CORRECT FOR |
| | THE RESUBMITTAL. |
| | FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | 6. PLEASE SEE ATTACHED FLORIDA STATUTE |
| | 533.80(2)(B) IN RESPECT WITH REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |