| 2007-02-07 11:43:12 | *** DENIED *** |
| | SEE MECHANICAL PLAN PAGE M-1. |
| | |
| | 1) UNIT 708 1ST. FL. BEDROOM 1, RETURN AIR TRANSFER |
| | DUCT IS LISTED AS A RETURN AIR TRANSFER GRILL, PLEASE |
| | CORRECT. |
| | |
| | 2) SAME UNIT PLEASE SHOW SIZE OF RETURN AIR TRANSFER |
| | DUCT (FLEX). |
| | |
| | 3) UNIT 708 2ND. FL., ALL RETURN AIR TRANSFER DUCTS ARE |
| | LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT. |
| | |
| | 4) SAME UNIT, PLEASE SHOW SIZE OF RETURN AIR TRANSFER |
| | DUCTS (FLEX). |
| | |
| | 5) UNIT 708 -1/2 A,ALL RETURN AIR TRANSFER DUCTS ARE |
| | LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT. |
| | |
| | 6) SAME UNIT, 7" RETURN AIR TRANSFER DUCTS (FLEX) ARE |
| | UNDER SIZED FOR BEDROOMS, BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| | SPACE IT'S SERVING AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN |
| | AIR BALANCE. PER 2004 FBC/R M1602.4 . |
| | |
| | 7) UNIT 708 - 1/2 B, 12X6 RETURN AIR TRANSFER GRILL TO |
| | BEDROOM 1 IS UNDER SIZED, BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R |
| | M1602.4 . |
| | |
| | 8) PLEASE ALSO SHOW SENSIBLE BTU'S IN A/C EQUIPMENT |
| | LISTING ON MECH. PLANS. |
| | |
| | 9) PLEASE SUBMITMANUAL J CALCULATIONS, PER 2004 FBC |
| | 13-607.1.ABC.1 . |
| | |