Plan Review Notes For Permit 06030498
Permit Number 06030498
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-10 00:00:00 
  
 NONCOMPLIANT
  
 IT IS UNCLEAR WHAT THE SCOPE OF WORK IS
 AS WAS COMMENTED ON BEFORE. SHEET E-1
 INDICATES A NEW 150 AMP PANEL, BUT THE
 FEED CONDUCTORS ARE TOO SMALL FOR 150
 AMPS PER 310.15(B)(6). THE EQUIPMENT
 GROUND IS TOO SMALL, 250.122.
  
 THERE IS NO INDICATION OF THE LOCATION
 OF THE REFERENCED SERVICES. SHOW THE
 PHYSICAL LOCATION OF ALL SERVICE
 EQUIPMENT ON THE PLAN. 215.5.
  
 THE TITLE BLOCK OF THE ARCHITECTURAL
 FIRM MUST CONTAIN THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED BY THE
 STATE PER 61G1-16.004(2).
  
 PLEASE RESUBMIT WITH THE ORIGINAL
 APPLICATION AS THE ONE SUBMITTED WITH
 THIS RESUB IS A PHOTOCOPY AND DOES NOT
 CONTAIN ORIGINAL SIGNATURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]