| Plan Review Notes For Permit 06030498 |
| Permit Number |
06030498 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | IT IS UNCLEAR WHAT THE SCOPE OF WORK IS | | | AS WAS COMMENTED ON BEFORE. SHEET E-1 | | | INDICATES A NEW 150 AMP PANEL, BUT THE | | | FEED CONDUCTORS ARE TOO SMALL FOR 150 | | | AMPS PER 310.15(B)(6). THE EQUIPMENT | | | GROUND IS TOO SMALL, 250.122. | | | | | | THERE IS NO INDICATION OF THE LOCATION | | | OF THE REFERENCED SERVICES. SHOW THE | | | PHYSICAL LOCATION OF ALL SERVICE | | | EQUIPMENT ON THE PLAN. 215.5. | | | | | | THE TITLE BLOCK OF THE ARCHITECTURAL | | | FIRM MUST CONTAIN THE CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED BY THE | | | STATE PER 61G1-16.004(2). | | | | | | PLEASE RESUBMIT WITH THE ORIGINAL | | | APPLICATION AS THE ONE SUBMITTED WITH | | | THIS RESUB IS A PHOTOCOPY AND DOES NOT | | | CONTAIN ORIGINAL SIGNATURES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|