| 2006-05-18 00:00:00 | |
| | DENIED |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE SCOPE OF WORK ON THE APPLICATION |
| | IS INTERIOR WALL RENOVATION. THE |
| | ELECTRICAL SHEETS DO NOT INDICATE |
| | EXISTING FROM NEW WORK. THEREFOR IT |
| | WOULD APPEAR THE UNITS ARE TO BE |
| | REWIRED. PLEASE INDICATE SAME ON THE |
| | APPLICATION AND INCREASE VALUE TO |
| | REFLECT SAME. IF SOME IS EXISTING AND |
| | SOME IS NEW PLEASE INDICATE SAME AT THE |
| | DEVICES. |
| | |
| | 2} THERE IS NO RECORD IN CITY HALL'S |
| | FILES THAT WOULD INDICATE ELECTRICAL |
| | UPGRADES. PLEASE PROVIDE LOAD |
| | CALCULATIONS, PANEL SCHEDULES, AND THE |
| | LOCATION OF ALL SERVICE EQUIPMENT, |
| | INCLUDING METERS, DISCONNECT AND PANELS |
| | PER 215.5. SEE 2002 NEC., 2004 |
| | RESIDENTIAL BUILDING CODE, AND NFPA-72. |
| | |
| | 3} PLEASE SEE RECEPTALE SPACING AND |
| | LOCATION REQUIREMENTS, NEC 2002, IF |
| | REWIRING. SEE EXISTING BUILDING CHAPTERS |
| | FOR INFORMATIION. |
| | |
| | COMPLY WITH THESE DOCUMENTS AND RESUBMIT |
| | FOR REVIEW. |
| | |
| | "ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS, AND LICENSE NUMBER |
| | ON EACH SHEET." 61G15-23.002 FAC. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |