2006-07-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_ 9.ON THE ANCHORING SCHEDULE,
 YOU HAVE INDICATED THAT THIS APPLICATION
 IS POURED CONCRETE.AREN'T THERE FILLED
 CELLS AT SOME OF THE OPENINGS?
  
 THE ANCHORING OF 16" IS NOT CODE
 COMPLIANT FOR FILLED CELLS/HOLLOW BLOCK.
 YOU HAVE SPECIFIED 2.5IN EDGE DISTANCE,
 BUT THIS DIMENSION IS NOT ON THE
 ANCHORING SCHEDULE.
  
 _XX_10.)NOTE THAT THERE WAS ONLY ONE
 PRODUCT APPROVAL SUBMITTED, WHICH I
 BELIEVE IS DIFFERENT FROM THE ONE
 PREVIOUSLY SUBMITTED.THE RESUB SHEET
 STATES "ADDED PRODUCT APPROVALS" BUT YOU
 HAVE REPLACED THE PREVIOUS PRODUCT
 APPROVAL.THIS IS ACCEPTABLE; BUT TO
 AVOID DELAYS IN THE FIELD I AM
 CONFIRMING THAT THIS IS YOUR INTENT.