| 2006-03-16 00:00:00 | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE CORRELATE CIRCUITING, |
| | CONDUCTOR SIZES, LOADS, FROM PANEL |
| | SCHEDULE TO LOAD CALCULATIONS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE INCLUDE ALLMININUM |
| | CONDUCTOR SIZES ON PANEL SCHEDULES. |
| | PLEASE SEE THESE ARE SHOWN AS BLANK AT |
| | THIS TIME. |
| | PLEASE SEE NOTES PERTAINING TO THE SIZES |
| | SHOWN ON LOAD CALCS, MANY ARE 15A |
| | CIRCUITS W/ #12 AWG AND SOME ARE NOTA |
| | LARGE ENOUGH FOR THE MIN REQ'D. |
| | 215.5.310.16.240.4 |
| | |
| | 3)NOTE: PLEASE SEE MIN REQURIED DEDICATE |
| | BATH (S) CIRCUITS PER 210.52D,210.11C3. |
| | SHALL BE A MIN OF #12/ 20A. |
| | |
| | 4)NOTE: PLEASE SEE NUMEROUS SINGLE POLE |
| | CIRCUITS WHICH ARE SHOWN AS 2-POLE |
| | CIRCUITS ON PANEL SCHEDULE? PLEASE |
| | CORRECT AND CORRELATE. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE CU SHOWS A DISCONNECT |
| | AND A 220V RECEPT FOR CU?? |
| | PLEASE CLARIFY WHAT THIS 22V RECEPT IS |
| | FOR? |
| | 440.11. |
| | |
| | 6)NOTE: PLEASE SEE WATER HEATER IS BEING |
| | SHOWN WITH A RECEPT FOR UNIT. PLEASE SEE |
| | 422.31 WHICH REQUIRES A DISCONNECT. |
| | PLEASE SHOW. |
| | |
| | 7)NOTE: PLEASE CORRELATE RISER, PLANS, |
| | AND PANEL SCHEDULE. |
| | PLEASE SEE RISER SHOWS A FEED FROM THE |
| | MCB PANEL TO ???? |
| | PLEASE SEE PLANS DO NOT SHOW THE METER. |
| | PLEASE SEE RISER NEEDS TO REFLECT |
| | CONDUIT FROM METER TO MCB UNDERGROUND, |
| | OR IF NOT UNDERGROUND, THEN A MAIN |
| | DISCONNECT WITH OCP WILL BE REQUIRED |
| | OUTSIDE. |
| | 230.70,230.6 |
| | PLEASE ALSO INDICATE THE AIC RATINGS FOR |
| | ANY NEW DISCONNECTS. 110.9,215.5 |
| | |
| | 8)NOTE: PLEASE SEE "GFI" NOT E ON PLANS |
| | WHICH MENTIONS ALL RECEPTS W/IN 15' FROM |
| | POOL TO BE GFI. THIS IS NOT CORRECT, |
| | PLEASE SEE 680.22 FOR MIN DISTANCE |
| | REQUIRED. |
| | |
| | 9)NOTE: PLEASE SHOW AND LABEL ALL ROOM |
| | AND AREA DESIGNATIONS ON ELECTRICAL |
| | PLANS. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SEE BATH RM WHICH DOES |
| | NOT SHOW THE SWITCH CONTROL TO THE LT/ |
| | FAN. |
| | 210.70 |
| | |
| | 11)NOTE: PLEASE SEE A RECEPT IN WHAT MAY |
| | BE THE DINING ROOM, WHICH SHOWS THE |
| | RECEPT BEING SWITCHED. PLEASE SEE |
| | 210.52B1,210.70, THIS IS NOT PERMITTED |
| | IN THE DINING AREA. THESE RECEPTS MUST |
| | BE PART OF THE ONE OR MORE SMALL |
| | APPLIANCE CIRCUITS. |
| | PLEASE ADJUST. |
| | |
| | 12)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 13)NOTE: PLEASE SEE 210.8A2 FOR GARAGE |
| | RECEPTS. |
| | |
| | 14)NOTE: PLEASE SEE KITCHEN PLANS |
| | INDICATE TWO GFI RECEPTS UNDER KITCHEN |
| | COUNTER? , IF THESE ARE FOR THE |
| | DISHWASHER OR DIPOSAL, THESE WOULD BED |
| | DEDICATED RECEPTS/ NON-GFI. |
| | PLEASE SEE 210.52C1 AS KITCHEN COUNTER |
| | SPACE MAY SEEM TO INDICATE COUNTER AT |
| | POSSIBLY BEING OVER 4' WHICH WOULD |
| | REQUIRE AN ADDTIONAL GFI RECEPT ON |
| | COUNTER. |
| | |
| | 15)NOTE: PLEASE SEE MANY RMS CONTAIN |
| | WHAT APPEARS TO BE A "J-BOX" , HOWEVER |
| | PLEASE SEE THIS SYMBOL IS NOT SHOWN ON |
| | SYMBOL SCHEDULE FOR USE/PURPOSE. |
| | |
| | 16)NOTE: PLEASE SEE THAT PLANS ARE |
| | REQUIRED TO CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS. |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS.471,481,489 ETC |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |