| 2006-04-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOC. |
| | |
| | 2- A) SURVEY WAS PREPARED FOR MORTGAGE |
| | ONLY, IT CAN'T BE USED FOR PERMITTING. |
| | SEE GENERAL NOTE #12. NEED SURVEY FOR |
| | PERMITTING PURPOSES. |
| | B) SURVEY TO HAVE ORIGINAL SIGNATURE |
| | AS REQUIRED BY CHAPTER 472 FL. STATUTE. |
| | |
| | 3- PROVIDE DRAINAGE PLAN AS REQUIRED BY |
| | SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| | |
| | 4- SHEET A-1: A) CLARIFY EXTERIOR |
| | ELEVATIONS. ROOF PITCH IS DRAWN TO 6:12, |
| | WHILE WRITTEN PITCH CALLS FOR 4:12. |
| | REVISE AS REQ'D. |
| | B) SQUARE FOOTAGES DON'T MATCH ACTUAL |
| | SQUARE FOOTAGES SHOWN ON FLOOR PLAN. |
| | REVISE SQUARE FOOTAGE AREAS AND TOTAL |
| | SQUARE FOOTAGE TO MATCH 1ST FL PLAN. |
| | PROJECT VALUATION WILL BE CALCULATED |
| | AFTER CORRECT SQUARE FOOTAGE IS PROVIDED |
| | AND ADDITIONAL FEES MAY BE DUE. |
| | C) REVISE TOP OF LINTEL ELEVATION. |
| | 8'-0" HIGH DOORS DON'T FIT IF TOP OF |
| | LINTEL IS AT 8'-0". |
| | D) CLARIFY WHAT'S THE BLACK SOLID |
| | LINE SHOWN ON ARCHED WINDOW BETWEEN |
| | SINGLE HUNG WINDOW & ARCHED WINDOW. |
| | |
| | 5- SHEET A-2: A) FOUNDATION PLAN AND |
| | FIRST FLOOR PLAN ARE MISSING STEP AT |
| | ENTRY PORCH, GARAGE SIDE DOOR AND REAR |
| | SLIDING GLASS DOORS. |
| | B) CLARIFY IF WATER HEATER AND A/C |
| | ARE LOCATED ON AN ELEVATED AREA FROM |
| | GARAGE FINISH FLOOR.IF SO, FOOTING |
| | DOESN'T MATCH. REVISE AS REQUIRED. |
| | C) SPECIFY ATTIC LOCATION AND SIZE. |
| | SEC. R807 2004 RESIDENTIAL CODE. |
| | D) SPECIFY CONCRETE SLAB CONTROL |
| | JOINTS OR WWM SUPPORTS AND SPACING AS |
| | REQ'D BY SEC. R506.2.4 2004 RESIDENTIAL |
| | CODE EXCEPTION #2. |
| | E) PROVIDE BATHROOM WITH DOOR THAT |
| | ALLOWS 29" MIN. CLEAR OPENING. SEC. R322 |
| | 2004 RESIDENTIAL CODE. |
| | F) SPECIFY TYPE OF GARAGE DOOR AS |
| | REQUIRED BY SEC. R309.12004 RES. CODE. |
| | G) ARCH FRAME DETAIL: SPECIFY HOW LONG |
| | ARE THE 1/2" WEDGE ANCHORS AND CLARIFY |
| | FASTENER FOR DIAGONAL BAR. SEE COMMENTS |
| | ON PLAN. SEC. 106.1.2CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 6- SHEET A-3: REVISE TRUSS ANCHOR |
| | SCHEDULE. NUMBER OF FASTENERS AND LOADS |
| | SPECIFIED FOR HLPTA-75 DON'T MATCH USP |
| | CATALOGUE. SEE CURRENT CATALOGUE AND |
| | PRODUCT APPROVAL. REVISE AS REQUIRED. |
| | |
| | 7- SHEET D-1:TYPICAL 1 STORY SECTION: |
| | A) REVISE EAVE DETAIL. DRAWN |
| | INCORRECTLY. NEED TO SHOW TRUSS LEG. |
| | B) SPECIFY ROOF VENTILATION AS REQ'D |
| | BY SEC. R806 2004 RESIDENTIAL CODE. |
| | C) WHAT'S SBXR-30? |
| | D) WINDOW SILL SHOWN DOESN'T MATCH |
| | SPECIFICATIONS. |
| | E) SPECIFICATIONS FOR ROOF SHEATHING |
| | DON'T MATCH THOSE SHOWN IN THE ROOF/WALL |
| | SHEATHING TABLE ON SAME PAGE. REVISE AS |
| | REQUIRED. |
| | F) WHERE IS THE UPLIFT TABLE FOR |
| | REBAR SPACING? |
| | |
| | 8- REVISE ALL GENERAL NOTES ON SHEET |
| | D-1. SEE CHAPTER 43 OF 2004 RESIDENTIAL |
| | CODE FOR ADOPTED STANDARDS AND EDITIONS |
| | TO BE USED. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ARCHED FIXED WINDOW. NEED 2004 |
| | FLORIDA CODE VERSION AND DRAWINGS WERE |
| | NOT SUBMITTED IN THIS PACKAGE. |
| | B) GARAGE SIDE DOOR. |
| | C) ENTRY DOOR. NEED 2004 FLORIDA CODE |
| | VERSION AND DRAWINGS ARE MISSING TOO. |
| | ***NOTE: ENGINEER OF RECORD TO REVIEW |
| | AND APPROVE ABOVE MENTIONED PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL. |
| | |
| | 10-STORM SHUTTERS: A) NEED 2004 FLORIDA |
| | CODE VERSION. |
| | B) DADE COUNTY NOA #03-0421.12 WAS |
| | SUPERSEDED. SEE DADE COUNTY WEBSITE. |
| | C) PROVIDE KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. SEE ATTACHED |
| | SAMPLE WHICH PROVIDES ALL REQUIRED |
| | INFORMATION FOR PLAN REVIEW. |
| | D) ENGINEER OF RECORD TO REVIEW |
| | PRODUCT APPROVAL AS REQUIRED BY SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- A) SOIL TEST REPORT WAS ADDRESSED TO |
| | PALM BEACH COUNTY. PROPERTY IS LOCATED |
| | IN THE CITY OF WEST PALM BEACH. REVISE |
| | AS REQUIRED. |
| | B) SEE 2004 RESIDENTIAL CODE FOR |
| | CORRECT CODE SECTION TO BE REFERENCED. |
| | AND REVISE AS REQUIRED. |
| | C) THERE WERE NOT ATTACHMENTS |
| | SUBMITTED IN THIS PACKAGE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |