| Plan Review Notes For Permit 06030376 |
| Permit Number |
06030376 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 250.32 TWO OR MORE BUILDINGS OR | | | STRUCTURES SUPPLIED FROM A COMMON | | | SERVICE. | | | (A) GROUNDING ELECTRODE. WHERE TWO OR | | | MORE BUILDINGS OR STRUCTURES ARE | | | SUPPLIED FROM A COMMON AC SERVICE BY A | | | FEEDER(S) OR BRANCH CIRCUIT(S), THE | | | GROUNDING ELECTRODE(S) REQUIRED IN PART | | | III OF THIS ARTICLE AT EACH BUILDING OR | | | STRUCTURE SHALL BE CONNECTED IN THE | | | MANNER SPECIFIED IN 250.32(B) OR (C). | | | WHERE THERE ARE NO EXISTING GROUNDING | | | ELECTRODES, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN PART III OF THIS ARTICLE | | | SHALL BE INSTALLED. | | | | | | PLEASE INDICATE ON THE RISER . | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|